Glossary of Terms
>
PCD
PCD =
P
rojected
C
onfiguration
D
ata
Configuration data stored in the device:
→ LPS and AS-i profile (IO, ID, ID1, ID2)
>
PDM
PDM =
P
rocess and
D
ialogue
M
odule.
Device for communication of the operator with the machine / plant.
>
PELV
PELV =
P
rotective
E
xtra
L
ow
V
oltage
Functional extra low voltage with safe separation, grounded variant of
→SELV. The specification as
PELV system to IEC 364-4-41 covers a measure to protect against direct and indirect contact with
dangerous voltages by a "safe separation" between primary and secondary side in the device (e.g.
power supply to PELV specification).
For this reason no separate PE conductor is required in a PELV system. It is allowed to ground circuits
and / or bodies in a PELV system.
>
Pictogram
Pictograms are figurative symbols which convey information by a simplified graphic representation.
(
→ chapter
What do the symbols and formats mean?
(
>
PLC configuration
Part of the CODESYS user interface.
► The programmer tells the programming system which hardware is to be programmed.
>
CODESYS loads the corresponding libraries.
>
Reading and writing the periphery states (inputs/outputs) is possible.
>
Polling
to poll = to count votes
The controller master fetches the data from every participant in the system successively:
1. Master calls participant 1.
2. Participant 1 replies with its current data (actual values).
3. Master transfers more data (target values) to participant 1, if needed.
4. Participant 1 acknowledges reception of the data.
etc. the same procedure for each further participant.
AS-i,
→cyclical polling: AS-i master cyclically polls the data of all →slaves in the →bus (see above).
The data is updated in the
→master after max. 5 ms. If →A/B slaves are used, the →cycle time can be
extended to 10 ms.
>
Power-on delay time
The time required by the controller K6 from the application of the voltage supply until all of the
following targets are reached:
both AS-i networks have reached normal operation
the master has read the configuration data of the CTTx slaves
the field buses can use the gateway (optional)
the PLC program was started (optional).