41
ifm
Device Manual AS-i IO-Link-Gateway (AC5225) Firmware V1.16
2017-11-20
IO-Link services
Device group services
>
Example event data
5263
This table is to give an overview of the error messages to be expected (excerpt).
Type
Source
Category
Mode
Event code
Value
[hex.]
Description
device PD invalid
device
error
displayed
PD_INVAL
FFF0
PD invalid event from the
device
device PD invalid
device
error
disappears
PD_INVAL
FFF0
PD invalid event disappears
from the unit
without details
device message
device
message
pulse
DEVICE
FF80
device warning
device
warning
pulse
DEVICE
FF80
device error
device
error
pulse
DEVICE
FF80
parameter error
device
error
pulse
PARAMETER
6320 from application listing
communication error
error
pulse
COMM
FF10
with details
Process data
address increment error
device
error
pulse
PD_INCR
FFE1 PD address missing
access outside PD
length
device
error
pulse
PD_LEN
FFE2 written or read PD too long
incomplete PD length
device
error
pulse
PD_SHORT
FFE3 written or read PD too short
reading on input
length 0
device
error
pulse
NO_PDIN
FFE4
writing on input length 0
device
error
pulse
NO_PDOUT
FFE5
System administration
display operating mode
master
message
pulse
NEW_SLAVE
FF21
Unspecific
wrong event display
master
error
pulse
Event
FF31
Application/Machine
save parameters
device
message
pulse
STORE_PAR
FF91
restore parameters
device
message
pulse
RESTORE_PAR
FF92
Com Startup request
device
message
pulse
RESTART_COM
FF98
detailed operating principle
TBD
application specific
device
message /
warning /
error
pulse / appears
/ disappears
xxxx for application listing
device = IO-Link device
master = IO-Link master