Device Manual AS-i IO-Link-Gateway (AC5225) Firmware V1.16
2017-11-20
IO-Link services
Device group services
>
IO-Link port parameters
5223
The projected port parameter defines the operating mode of the IO-Link port.
NOTE
When the scan mode is defined, the IO-Link master looks for an IO-Link device and activates the
respective COM mode as soon as a device has been found.
If a device is removed, the master sends a wake-up signal to detect new devices. To avoid this on
connected digital sensors or actuators the respective operating mode has to be projected.
Invalid parameters are discarded.
Since the changes are optional, a read process of the actual settings is required in a device-
independent driver after a write request. "Write device group OK" does not acknowledge the
requested settings but only the successful transmission.
Attribute
Coding [bin]
Value (write)
Value (read)
operating mode
nnnn 0001
nnnn 0010
nnnn 0011
nnnn 0100
nnnn 0101
nnnn 0110
0000 0000
digital input
digital output
scan mode
----
----
----
inactive
digital input
digital output
scan mode
COM1 mode
COM2 mode
COM3 mode
inactive
port cycle
nn00 nnnn
free
free