
(C) IDM ENERGIESYSTEME GMBH
6. Assembly and hydraulic installation
Installation instructions iPump A 3-11
28
The connection on refrigeration side
is not in the middle of the outdoor unit,
but slightly displaced. See the drawing
above.
assembly and hydraulic installation
SL-Modul
Variant 2
In this variant, the refrigerant lines are routed via the
cut-out for the condensate run-off under the outdoor
unit. The laying of the refrigerant lines from the right
or left side of the outdoor unit is not possible. The
load capacity of the base plate must be given.
6.4. Place of installation
If the place of installation is not protected from snow-
fall, it must be selected or designed such that the
lower edge of the outdoor unit is 20 cm above the
expected snow level in any case.
The outdoor unit must always be installed on a solid
surface in horizontal position. This can be achieved
with an extra concrete base or a wall bracket.
The loading capacity of the wall bracket must be
given. The unit must be
fi
xed with four screws M10.
Air heat pumps are producing condensation water
during operation. This could be 6 liters per defrost
cycle within 2 minutes. The condensate run-off must
be frost-proof.
In coastal installation, a minimum distance
of 5 km from the coast must be observed.
If this safety distance is not observed, the-
re could occur increased corrosion. These
cases are excluded from the guarantee.
The outdoor unit already includes a heated conden-
sate run-off tray to avoid freeze. The condensate run-
off also has to be heated, with the already mounted
heating cable.
On the exhaust side of the outdoor unit exists an in-
creased risk of frost. Rain pipes, water-carring pipes
or water-carring containers must not be located next
to the exhaust side.
%DVH
&RQGHQVDWH
UXQRII
&RQQHFWLRQV
5HIULJHUDQWOLQHV
Exhaust side
Suction side
View from below
'XFWIRU
5HIULJHUDQWOLQHV
To avoid damages caused by animals,
such as rodents or insects, all cable- and
pipe openings have to be closed.
Refrigerant
pipes
Condensate run-off
Suction side
Exhaust side