3.10. Filling quantity refrigerant
The iPump A 3-11 is pre-
fi
lled with refrigerant. Up to a distance of 6 m between indoor unit and outdoor unit no
refrigerant no additional needs to be re
fi
lled. For pipe length more than 6 m, the following refrigerant quantities
must be re
fi
lled.
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
1,1
0
2
4
6
8
10
12
14
16
18
20
Re
Ͳ
fill
quan
tity
in
[kg
]
Pipe
length
in
one
direction
[m]
Refrigerant
re
Ͳ
fill
quantity
iPump
A
3
Ͳ
11
Pipe
length
in
one
direction
[m]
Refrigerant
quantity
[kg]
Re
Ͳ
fill
quantity
[kg]
0
4,1
0
6
4,1
0
10
4,4
0,3
15
4,8
0,7
20
5,2
1,1
3.11. Maximum heigth dif ference
If the height difference between the indoor unit and outdoor unit is lower than 5 m no oil elevation arc must be
installed before the inclination. In case of a higher height difference the installation must be done after 5 m. The
oil elevation arc must be installed by a certi
fi
cated service technician. Whether the indoor unit or the outdoor
unit is higher, does not matter. The maximum height difference between indoor unit and outdoor unit is 10 m.
Version 1
Version 2
max 5 m
<5 m
max 5 m
max 5 m
max 5 m
Height difference lower than 5 m
Height difference more than 5 m