29
72-910-24 Revision H
MAINTENANCE
The only recommended maintenance required on your controller is periodic inspection of the
conductivity sensor. Clean the probe using a mild cleaning agent such as detergents or 5% HCl
(removes scaling deposits). It is recommended that you establish a regular maintenance schedule
designed to meet the needs of your particular application. All other service should be performed
by factory authorized personnel only. Modifications to or tampering with the circuit level
components makes all warranties, written or implied, and/or manufacturer’s responsibility for this
controller null and void.
DISCONNECT POWER BEFORE OPENING THE UNIT TO ACCESS FUSES
.
MAKE SURE
THAT REPLACEMENT FUSES ARE OF SAME TYPE TO MAINTAIN SAFTEY APPROVALS
.
FUSE
TYPE
F1 & F2
5 X 20mm, 5A, 250V
SPECIFICATIONS
Controller
Enclosure
NEMA 4X/IP67
Enclosure Dimensions
243.3 x 185 x 132 mm (9.58 x 7.28 x 5.20in)
Power supply
120 or 220 VAC; 50/60Hz.
Display
Backlit Temp-Comp LED Graphic Display, 64 x 128 pixels
Accuracy
+/- 2% of scale at point of measure
Maximum relay output current
120 VAC:
5 A Resistive/General use
4LRA/4FLA,1/10HP (motors)
220 VAC:
5 A Resistive/General use
Not rated for motors
Probe
Maximum temperature
392° F (200°C)
Temperature compensation range
32°F – 392°F (0° – 200°C)
Maximum pressure
210 PSI (14.5 BAR) of saturated steam
Probe type
Contact, 1.0 cell constant
Maximum cable length
500 Feet (150 Meters)
Thread size
1” NPT
Conductivity reading
0-20,000 uS/cm; 1 uS/cm increments
Temperature Sensor (*
optional
)
RTD = 1000 Ω (*
see NOTE: Sensor Connection Input
p.11)