26
72-910-24 Revision H
Cycle Timer Menu – Start Times
From this menu configure the days and weeks the timer will run for. Any combination of days and/or
weeks is acceptable for each timer.
- Select the timer start days and weeks by using the up and down buttons to the right of the
display. Move the cursor to the right or left by using the button to the bottom of the display. The
selected day or week will flash as the cursor is moved to each setting. The flashing On|Off text
indicates if the current setting is on or off.
- If a day or week is highlighted, or appears as reverse video, that particular day or week will
have biocide feed.
- The week # shown in the lower right of the display indicates which week number the co
ntroller’s time
is currently set to.
Factory Defaults
Parameter
Default
Configuration
Date Format
MM/DD/YY
Time Format
12hr Clock
Inputs
Dry Contact
Sample Mode
Timed
Interval
2:00 Hours
Sample Time
2:30 MM/SS
Set point
3000 uS/cm
Differential
100uS/cm
Water Meter Pulse Volume
100
Units
Gallons
Drum Levels
Pumps Run
Scrolling
3 Seconds
Display Contrast
26
Password
0000(disabled)
Settings
Timer Modes
Disabled
Home Screen
Settings
Timer 1
ALL | SUN| MON| TUE
WED| THU| FRI | SAT
Days On|Off
Cancel |
Enter
Start times
ALL | EVN| ODD| 1ST
2ND | 3RD| 4TH |
Weeks On|Off Wk#2
Cancel |
Enter
Cycle Timer
Start Time 1
hh:mm
01:00A
Cancel |
Enter
Start time 1