24
72-910-24 Revision H
Timer Mode Menus
From this menu pick the mode that the inhibitor feed will follow.
Pulse Timer
– See the menu for this function in the following section.
Percent Timer
– Set the timer run time period and percentage of the time period.
Example: Cycle Time=60minutes, % Minutes to run=10, the timer will run for 10% of 60
minutes, or 6 minutes every 60 minutes.
28 Day Timer (Biocide)
– See the menu for this function in the following section.
Cycle Timer
- See the menu for this function in the following section.
Disabled
– Deactivates the timer
Alarm
– Timer 4 only, the relay will activate for any system alarm.
Timer Modes – Pulse Timer Menu
From this menu configure how you want the inhibitor to feed while in pulse timer mode. This mode uses the
water meter input to cause a counter to accumulate a certain volume of water before the inhibitor is feed. Once
the accumulated volume is reached the inhibitor is feed for the programmed Feed Time.
Feed Time
– Set this value to the amount of time you want the timer to run for when the water meter
accumulator reaches its target.
Accumulator Set
– Set this value to the amount of water that needs to accumulate prior to a timer run
time. The units will be in gallons or liters depending on what you set the water meter units to.
Accumulator Count
– This is the current running count of the water meter accumulator.
Water meter
– Select which of the five possible water meter inputs will activate the pulse timer.
Home Screen
Settings
Timer 1
Pulse Timer
Percent Timer
28 Day Tmr
Cycle Timer
Disabled
Back | Select
Home Screen
Settings
Timer 1
Feed Time
Accum Set
Accum Count
Water Meter
Back | Select
√Pulse Timer