18
72-910-24 Revision H
Gallons or Liters
Gal/lit
– Set how the controller should display the water meter units of measure.
Scrolling
From the Display Scrolling setting you can adjust how frequently the controllers display will scroll from
one timer’s status to the blowdown timers and conductivity readings on the home screen.
Scrolling
– Set the number of seconds to scroll.
Display Dampener
From the Display Dampener setting option you select how often you want the actual conductivity
reading updated on the Home Screen and dampening of the controller response to sudden changes in
conductivity. In the timed mode and sample and hold modes the reading only changes in real time
during the sample times and hold times.
Display Dampener
– Set this value to the number of seconds you want the controller to
dampen the displayed conductivity and controller response.
The controller takes a conductivity reading every second. Increasing this value above one
second causes the controller to average the readings, hence, slowing down the control
functions. In the timed mode and sample and hold modes the reading only changes in real time
during the sample times and hold times.
Display Contrast Setting
From the Display Contrast setting you adjust the display contrast to give the best clarity and readability
of the display screen.
Contrast
– Adjust this value up or down to give you the best display contrast.
Home Screen
Configure
Scrolling
Scrolling
03 Sec
Cancel |Enter
Home Screen
Configure
Gal/Lit
√Gallons
Liters
Cancel |Enter
Home Screen
Configure
Disp Damp
Display
Dampener
01 sec
Cancel |Enter
Contrast
Contrast
26
Cancel |Enter
Home Screen