Technical Specifications
A-10
IDEC SmartRelay User’s Manual
FL1A-H12RCE
FL1A-B12RCE
Digital outputs
Number
4
Output type
Relay outputs
Electrical isolation
Yes
In groups of
1
Activation of digital input
Yes
Output voltage
Output current
Continuous current I
th
(per
connector)
Max. 10 A
Incandescent lamp load (25,000
switching cycles) at
1000 W
Fluorescent tubes with electr.
control gear (25,000 switching
cycles)
10 x 58 W
Fluorescent tubes,
conventionally compensated
(25,000 switching cycles)
1 x 58 W
Fluorescent tubes,
uncompensated (25,000
switching cycles)
10 x 58 W
Short circuit-proof and overload-
proof
Short-circuit current limitation
Derating
None throughout the entire temperature
range
Short circuit-proof cos 1
Power protection B16
600A
Short-circuit proof cos 0.5 to 0.7
Power protection B16
900A
Parallel switching of outputs to
increase power
Not permitted