IDEC SmartRelay Functions
4-34
IDEC SmartRelay User’s Manual
Seven–day time switch: example
The output of the seven–day time switch is to be switched
on every day from 05:30 to 07:40. In addition, the output is
also to be switched on from 03:10 to 04:15 on Tuesday and
from 16:30 to 23:10 at the weekend.
Three cams are required for this.
Here is the parameter assignment window for cams 2 and
3 from the above timing diagram.
Cam 1
Cam 1 switches on the output of the seven–day time switch
every day from 05:30 to 07:40.
Cam 2
Cam 2 switches on the output of the seven–day time switch
every Tuesday from 03:10 to 04:15.
B01:No1
D=
On =05:30
Off=07:40
B01:No2
D=-T-----+
On =03:10
Off=04:15