background image

393231

Bulletin B1867

902 MHz Wireless Relays Application Manual

Getting Started

•  Plan where you will mount each receiver and transmitter.
       •  Avoid transmitting along a length of wall, sharp angles and large obstructions.
       •  Avoid mounting inside a metal enclosure.
       •  Typical range is 100’ line of sight.
•  Link devices to each other before installing. 
       •  All RIBs must be powered during Link.
•  RIBWxxxB-EN3 is both a transmitter and a receiver. 
•  RIBWxxC-EN3 is only a receiver.
•  Linking a RIB with another RIB puts the pair in Bi-directional mode.
•  PHC Gateway Controller can also link with a RIB and be Bi-directional.
•  Relay output state is saved at power loss. Relay output is restored when power is recovered.  
    (Exception: RIBW24B-EN3 will not save last state when powered from 24Vdc). 
•  Each Relay can be Linked to up to 30 transmitters of any combination.

page 1

902 MHz Model

Power Input  (Vac)

Contact Rating (A)

Transmission Source       

EEP

RIBW24B-EN3

24 ac/dc

20

Dry-Contact

A5-30-02

RIBW01B-EN3

120

20

Dry-Contact

A5-30-02

RIBW208-EN3

208

20

Dry-Contact

A5-30-02

RIBW240B-EN3

240

20

Dry-Contact

A5-30-02

RIBW277B-EN3

277

20

Dry-Contact

A5-30-02

RIBW01C-EN3

120

5

NA

A5-30-02

RIBW02C-EN3

208-277

5

NA

A5-30-02

WDWS-EN3

None

NA

Contact Closure

D5-00-01

WWS-EN3

None

NA

Button Press

F6-02-02

Device

EEP

PHC Gateway Controller

A5-38-08

Keycard

F6-02-02

Occupancy Sensor

A5-07-01

Compatible Devices from other Manufacturers

RIBWxxxB-EN3

RIBWxxC-EN3

WDWS-EN3

WWS-EN3

Reviews: