![IDEC HR6S-AF Original Instructions Manual Download Page 27](http://html1.mh-extra.com/html/idec/hr6s-af/hr6s-af_original-instructions-manual_3664627027.webp)
Technical Data
HR9Z-B2192 8/2020
27
Start Input
Classification of Safety-Related Inputs and Start Input as per ZVEI CB24I
Representation and values as per identifying key, ZVEI CB24I:
Refer to Dynamization of Safety-Related Inputs and Start Input
) for test pulse times.
Characteristic
Value
Output voltage at DC+
>15 VDC
Input voltage at CH+
0 ... 24 VDC (+20 %)
Switching voltage activate CH+
>15 VDC
Switching voltage deactivate CH+
<5 VDC
Input current
5 mA
Maximum wire resistance
500 Ω
Source/sink
Interface type
Additional measure
Source/sink
Interface type
Sink:
A
M
Source:
C0
Interface type A: Sink
Parameter
Minimum value
Maximum value
Input current Ii (in the ON state)
3 mA
5 mA
Output voltage Ui
15 V
24 V (+20 %)
Additional measure M
The inputs are not types as per
IEC 61131-2.
TG is S#1 for S#2.
TG is Y1 for Y2.
>15 VDC