Technical Data
HR9Z-B2192 8/2020
29
Timing Data
Maximum Response Times
Recovery Time
Switch-On and Activation Delays
Monitored Start
Dynamization of Safety-Related Inputs and Start Input
Characteristic
Value
Maximum response time to request at safety-related input 20 ms
Maximum response time after power outage AC
200 ms
Maximum response time after power outage DC
120 ms
Characteristic
Value
Recovery time after request at safety-related input
200 ms
Characteristic
Value
Switch on delay after power on and automatic start
2500 ms
Delay after activation of safety-related input or valid start
condition
100 ms
Characteristic
Value
Waiting time
2500 ms
Minimum duration of start pulse for monitored start
80 ms
Characteristic
Value
Test pulse duration (safety-related input must be activated
for longer than duration of test pulse)
2 ms
Test pulse interval
500 ms
Maximum delay of test pulse
40 ms
Test pulse phase shift
At least 70 ms