![IDEC HR6S-AF Original Instructions Manual Download Page 78](http://html1.mh-extra.com/html/idec/hr6s-af/hr6s-af_original-instructions-manual_3664627078.webp)
Diagnostics
78
HR9Z-B2192 8/2020
LED ERROR - Detected Errors
This LED lights solid in conjunction with additional LEDs to indicate detected errors. In the case of
a detected error, the device transitions to the defined safe state. You must remove the cause of
the detected error and perform a power cycle of the device to exit the defined safe state and
resume operation. Contact your IDEC CORPORATION service representative if the condition
persists.
State
In conjunction with additional
LEDs
Meaning
Remedy
Additional LEDs State of
additional LEDs
Solid on
STATE,
START and S##
Flashing
synchronously
General error detected.
Verify correct wiring.
Solid on
STATE,
START and S##
Solid on
Configuration error
detected.
Verify that the positions of the
selectors are appropriate for the
application to be implemented.
Solid on
POWER
Flashing
Power supply error
detected.
Verify correct wiring.
Use a suitable power supply.
Solid on
STATE
Flashing
Error detected at safety-
related output.
Perform a power cycle.
Solid on
START
Flashing
Cross circuit detected at
start input.
Verify correct wiring.
Solid on
STATE and
START
Flashing
synchronously
Error detected at safety-
related output of
extension module.
Perform a power cycle.
Solid on
S##
Flashing
Cross circuit detected at
safety-related input (for
example, incorrect wiring
or application function
with dynamization
selected, but
dynamization not
supported by connected
sensor/device).
Verify correct wiring.
Verify correct configuration.
Solid on
S## and S##
Flashing
synchronously
Cross circuit detected at
safety-related inputs (for
example, incorrect wiring
or application function
with dynamization
selected, but
dynamization not
supported by connected
sensor/device).
Verify correct wiring.
Verify correct configuration.
Summary of Contents for HR6S-AF
Page 1: ...http www idec com HR6S AF Safety Module Original instructions HR9Z B2192...
Page 8: ...8 HR9Z B2192 8 2020...
Page 14: ...14 HR9Z B2192 8 2020...
Page 20: ...Introduction 20 HR9Z B2192 8 2020...
Page 46: ...Engineering 46 HR9Z B2192 8 2020...
Page 56: ...Installation 56 HR9Z B2192 8 2020...
Page 82: ...Diagnostics 82 HR9Z B2192 8 2020...