Technical Data
HR9Z-B2192 8/2020
31
Data Functional Safety
Data Functional Safety
Characteristic
Value
Defined safe state
Safety-related outputs are de-energized
Normally Open: open
Maximum Performance Level (PL), Category
(as per ISO 13849-1:2015)
Normally Open: PL e, Category 4
Actual PL and category depend on wiring and
configuration.
Maximum Safety Integrity Level (SIL)
(as per IEC 61508-1:2010)
Normally Open: 3
Actual SIL depends on wiring and configuration.
Safety Integrity Level Claim Limit (SILCL)
(as per IEC 62061:2005+AMD1:2012+AMD2:2015)
Normally Open: 3
Actual SILCL depends on wiring and configuration.
Type
(as per IEC 61508-2)
B
Hardware Fault Tolerance (HFT)
(as per IEC 61508 and IEC 62061)
1
Stop Category for Emergency Stops
(as per ISO 13850 and IEC 60204-1)
0
Lifetime in years at an ambient temperature of 55 °C (131 °F)
(as per IEC 61508)
20
Safe Failure Fraction (SFF)
(as per IEC 61508 and IEC 62061)
>99 %
Probability of Dangerous Failure per hour (PFH
D
) in 1/h
(as per IEC 61508 and ISO 13849-1)
1.13 x 10
-9
Mean Time To Dangerous Failure (MTTF
D
) in years
(high as per ISO 13849-1)
>30
Average Diagnostic Coverage (DC
avg
)
(high as per ISO 13849-1)
≥99 %
Maximum number of cycles over lifetime
DC-13, 24 VDC 1 A: 1,200,000
DC-13, 24 VDC 3 A: 180,000
AC-1, 250 VAC 4 A: 180,000
AC-15, 250 VAC 1 A: 70,000
AC-15, 250 VAC 3 A: 39,000
Summary of Contents for HR6S-AF
Page 1: ...http www idec com HR6S AF Safety Module Original instructions HR9Z B2192...
Page 8: ...8 HR9Z B2192 8 2020...
Page 14: ...14 HR9Z B2192 8 2020...
Page 20: ...Introduction 20 HR9Z B2192 8 2020...
Page 46: ...Engineering 46 HR9Z B2192 8 2020...
Page 56: ...Installation 56 HR9Z B2192 8 2020...
Page 82: ...Diagnostics 82 HR9Z B2192 8 2020...
Page 88: ...Accessories Service Maintenance and Disposal 88 HR9Z B2192 8 2020...