![IDEC HR6S-AF Original Instructions Manual Download Page 64](http://html1.mh-extra.com/html/idec/hr6s-af/hr6s-af_original-instructions-manual_3664627064.webp)
Functions
64
HR9Z-B2192 8/2020
Application Function 6
Synchronization:
Wiring of the inputs for sensors/devices with OSSD outputs
Characteristic
Value/Description
Typical applications
Monitoring of electro-sensitive protective
equipment such as type 4 light curtains as per
IEC 61496-1
Monitoring of RFID sensors
Type of outputs of sensor/device providing the input signal
for application function
OSSD (Output Signal Switching Device) outputs
S## terminals to be connected
S12 and S22
Dynamization
No
Signal interlock monitoring
Between terminals S12 and S22
Synchronized terminals
Synchronization time
S12 synchronized with S22
S12 and S22 have to be activated within 0.5 s.