welcome to our ideology

SYSTEM CONFIGURATIONS

The Multiline Flue Cascade is one of the latest additions to the flue accessory range from Ideal, 

designed specifically for the Evomax 2 range. Available for installations up to 600kW as both a 

starter kit and extension pack the Multiline system enables Evomax 2 boilers installed as open 

flue to be connected via a common flue header. This creates a single flue connection point for 

a flue specialist to design to knowing that the boiler installation is efficient and safe.

The Cascade flue system is supplied in two kits. A Starter Kit & an Extension Kit.
Wire retaining clips are also provided to prevent movement of the tube connections 

due to expansion and contraction. These must be fitted to the ductwork to ensure safe 

operation of the system.

•  Simple system ordering with a 

starter kit and extension kits

•   Starter kit includes, appliance 

connection, non-return flue 

damper, condensate tee and trap 

and all clips to secure the flue

•  Extension pack includes appliance 

connection, non-return flue 

damper, and all clips to secure the 

flue

•  Available for both 80/125 & 100/150 

flue adaptor applications

• For installations up to 600kW
• Type B23 flue
•  Designed specifically to work  

efficiently with Evomax 2 boilers 

with commissioning simply 

completed by selecting Multiline  

flue from the installer set up menu

•  The perfect addition for Evomax 2 

installations using either the 

standard height or low frame and 

header kits

PRODUCTS

STARTER KIT

EXTENSION KIT

1

End Cap

R

2

Siphon / Condensate trap

R

3

Collector Pipe (200 dia)

R

R

4

Elbow (90 x 100)

R

R

5

Expander (80/125 flue adaptor kits only)

R

R

6

Flue Extension Tube (80 or 100)

R

R

7

Air Intake Grill

R

R

OPTION

GAS TYPE

EVOMAX MODELS

MAX NUMBER  

OF BOILERS

MAX SYSTEM

CAPACITY

1

Natural gas

Combinations of 100,

120, 150

6

600kW

2

Combinations

that include a

30, 40, 60 or 80

6

400kW

3

Propane

Combinations of 100P 

or 120P

6

 600kW

4

Combinations of

30P, 40P, 60P, 80P

6

400kW

MULTILINE CASCADE

OPERATION

1

2

3

4

5

6

7

EXAMPLE 3 (OPEN FLUE)

EXAMPLE 4 (CONCENTRIC)

OPEN FLUE FOR EVOMAX 2 30

Resistance (m)

Flue Size

80

Max permissible flue run

65

2 x 45˚ elbow

2 x 0.45 = 0.9

Total Flue Resistance

65 - 0.9 = 64.1

HORIZONTAL FLUE FOR EVOMAX 2 120

Resistance (m)

Flue Size

100/150

Max permissible flue run

9

2 x 90˚ elbow

2 x 1.9 = 3.8

Total Flue Resistance

9 - 3.8 = 5.2

b

9

5

3

5-

0

1

2

6

0

2

EXAMPLE 2 (CONCENTRIC)

VERTICAL FLUE FOR EVOMAX 2 80

Resistance (m)

Flue Size

80/125

Max permissible flue run

10

2 x 45˚

2 x 0.85 = 1.7

Total Flue Resistance

10 - 1.7 = 8.3

Summary of Contents for EVOMAX 2 Series

Page 1: ...1 idealheating com EVOMAX 2 CONDENSING BOILER PRODUCT FLUE GUIDE H E A T I N G idealheating com welcome to our ideology Commercial Industrial Heating Product of the Year 2020...

Page 2: ...its Hull manufacturing plant and offices since 1906 Ideal is one of the few true British manufacturers left in the heating industry Your phone or tablet can let you appreciate our Condensing Boiler ra...

Page 3: ...5 year warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Heating Terms and conditions available at idealheating com 5 DOWNLOAD...

Page 4: ...warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Heating Terms and conditions available at idealheating com 1 3 4 5 7 6 8 9...

Page 5: ...Fuse Rating A 4 0 Power Consumption W 81 138 82 149 187 243 240 IP Rating IPX4D Nominal Flue Size concentric mm 80 125 100 150 Condensate Drain mm 25 Water Content l 3 0 5 0 7 0 9 2 Dry Weight Kg 47 5...

Page 6: ...perature differentials SOURCING The condensing boiler must be manufactured or finally assembled in the United Kingdom CASCADE The boiler must be configurable up to 6 boilers max 900kW in cascade using...

Page 7: ...ilers A Low Height Inline cascade can be for up to 4 boilers 1 Standard Height Frame required for each boiler in the cascade 1 pump required for each boiler in the cascade The wide range of options av...

Page 8: ...394 DN65 209395 DN80 219552 DN100 219553 DN150 219554 Magnetic Low Loss Mixing Header MLLH DN50 222191 DN65 222192 DN80 222193 DN100 222194 Plate Heat Exchanger Up to 60kW total output DN50 222219 Up...

Page 9: ...0 1950 to top of Frame 1918 to top boiler 300 650 1100 25 1480 25 530 850 574 120kW 560 456 664 150kW 212 200 380 2 BSP Female Gas Connection 1950 to top of Frame 1918 to top boiler 300 650 1650 25 25...

Page 10: ...0 6 x Evomax 2 boilers 120 150kW with LLH separation UIN DN FLANGE SIZE SUITABLE FOR 221127 DN50 1 x Evomax 2 boilers 30 150kW with PHEX or M LLH separation UIN DN FLANGE SIZE SUITABLE FOR 221128 DN65...

Page 11: ...EXCHANGER UP TO 60KW TOTAL OUTPUT PLATE HEAT EXCHANGER Covering outputs of 60 150 300 450 600 750 and 900kW Brazed Plate Heat Exchangers ensure optimum heat transfer efficiency and low resistance with...

Page 12: ...300 470 466 UIN DN FLANGE SIZE 222223 DN50 222225 DN80 222995 DN100 UIN DN FLANGE SIZE 222226 DN80 222996 DN100 330 709 376 632 519 UP TO 600KW TOTAL OUTPUT PLATE HEAT EXCHANGER UP TO 750KW TOTAL OUT...

Page 13: ...number of kits required LOW LOSS HEADER STANDARD HEIGHT INSULATION STARTER KIT STANDARD HEIGHT INSULATION CONTINUATION KIT STANDARD HEIGHT INSULATION CONTINUATION KIT DN100 STANDARD HEIGHT IN LINE HE...

Page 14: ...er Kit 1 1 1 UIN DESCRIPTION 1 BOILER CASCADE 2 BOILER CASCADE 3 BOILER CASCADE 4 BOILER CASCADE 223032 Low Height Insulation Starter Kit DN50 1 223035 Low Height Insulation Starter Kit DN65 1 223038...

Page 15: ...his schematic is an illustration of a hydraulic arrangement for discussion and reference use only The schematic may not accurately describe the actual arrangement required in order for the system to o...

Page 16: ...30 EVOMAX 2 FLUE OPTIONS 31 idealcommercialboilers com...

Page 17: ...elbow Terminal Locking collars x2 Wall plates x2 CONTENTS Terminal Locking Collar Finishing plates x2 Bracket To comply with CE certification Evomax boilers must be fitted with Ideal concentric flues...

Page 18: ...261 Extension Kit 100 150 213262 Pitched Weather Collar 80 125 152609 Pitched Weather Collar 100 150 152610 Flat Weather Collar 80 125 152611 Flat Weather Collar 100 150 152612 90 Elbow 80 125 single...

Page 19: ...imum pressure drop allowed in the flue for that boiler The maximum pressure drop allowed in the flue is given below PERMISSIBLE FLUE LENGTH The maximum permissible flue lengths for each model are show...

Page 20: ...r installations up to 600kW Type B23 flue Designed specifically to work efficiently with Evomax 2 boilers with commissioning simply completed by selecting Multiline flue from the installer set up menu...

Page 21: ...eter extension tube D 90 degree elbow E Flue terminal end F External wall plate G Internal wall plate H Wall bracket Note The 100 150mm Plume Kit system can also be used on Evomax 80 80P 60 60P model...

Page 22: ...stream of heat exchanger Fan upstream of heat exchanger B open flue B1 appliance with a draught diverter B11 B12 B14 B13 B2 appliance without draught diverter B21 B22 B23 TYPE B22 TYPE B23 TYPE B11 T...

Page 23: ...creased The Act was an important milestone in the development of a legal framework to protect the environment Although smog is no longer an issue more recent editions of the Clean Air Act have maintai...

Page 24: ...ement The approved documents offer guidance on how to comply and are not legally binding unless the manufacturer of the appliance stipulates them in the installation manual It is prudent however to fo...

Page 25: ...rs instructions NOTES 1 It is most important that the correct concentration of the water treatment products is maintained in accordance with the manufacturers instructions 2 If the boiler is installed...

Page 26: ...10 410 610 155 205 305 Low level 310 410 610 155 205 305 620 820 1220 310 410 610 CONCENTRIC WALL TERMINAL POSITIONS MINIMUM SPACING A Below an opening 1 300mm B Above an opening 1 300mm C Horizontall...

Page 27: ...y 230V AC 50 60 Hz 0 8amps Alarm contact NC 4 Amps resistive Overheat protection 130 C Tank Capacity 2 0 Litres Maximum vertical head 4 5m Maximum horizontal length 30m IDEAL COMMERCIAL BOILERS CONDEN...

Page 28: ...icated national service team delivering help and advice to you and your customers throughout the year BOILER TRAINING Our comprehensive one day courses can be mixed and matched for individual installa...

Page 29: ...ry rights of the consumer are not affected PLEASE NOTE The information in this brochure was correct at the time of going to print Ideal Heating reserve the right to make any modifications to product s...

Reviews: