If the terminal is fitted less than 500 mm below plastic gutters, painted eaves or any other painted surface then an aluminium 

shield at least 1m long should be fitted to protect the surface. For positioning of open flue terminals reference should be made to 

BS5440 Pt. 1. In IE refer to I.S. 813:2002

Heat inputs in excess of 70kW nett. 

For boiler installations with total heat inputs in excess of 70kW nett, reference should be made to BS6644.  

In IE refer to I.S. 820:2000.

VENTILATION

The ventilation requirements of these boilers is dependant on the type of flue system used, and their heat input.  

All vents must be permanent with no means of closing, and positioned to avoid accidental obstruction by blocking  

or flooding.

EVOMAX 2 30/30P, 40/40P, 60/60P

Detail reference should be made to BS5440 Pt. 2. In IE refer to the current edition of I.S. 813.
The following notes are for general guidance only: If installed as a room sealed appliance in a room or internal 

space, then no purpose provided ventilation is required. If installed as an open flued appliance in a room or 

internal space then a permanent air vent is required. The sizes given below are for vents directly communicating 

with outside air. For other situations refer to BS5440 Pt. 2. In IE refer to the current edition of I.S. 813.

If installed in a compartment, then permanent air vents are required at high and low level. These vents may  

communicate direct to outside air, or to a room/internal space. If to a room/ internal space, it must itself be 

adequately ventilated as above.

EVOMAX 2 VENTILATION REQUIREMENTS (NOT EXCEEDING 70KW NET INPUT) WHEN 

INSTALLED IN A COMPARTMENT

The temperature within the boiler room shall not exceed 25˚C within 100mm of the floor, 32˚C at mid height and 
40˚C within 100mm of the ceiling.

ROOM SEALED APPLICATION - MIN. VENT FREE AREA (CM

²

)

OPEN FLUE APPLICATION - MIN. VENT FREE AREA 

(CM

²

)

TO A ROOM OR INTERNAL 

SPACE

TO OUTSIDE AIR

TO A ROOM OR INTERNAL 

SPACE

TO OUTSIDE AIR

Boiler 

Size

30

40

60

30

40

60

30

40

60

30

40

60

High 

Level

310

410

610

155

205

305

310

410

610

155

205

305

Low 

level

310

410

610

155

205

305

620

820

1220

310

410

610

CONCENTRIC WALL TERMINAL POSITIONS

MINIMUM SPACING

A.

 Below an opening (1)

300mm

B.

 Above an opening (1)

300mm

C.

 Horizontally to an opening (1)

300mm

D.

 Below gutters, soil pipes or drain pipes

75mm

E.

 Below eves

200mm

F.

 Below balcony or car port roof

200mm

G.

 From a vertical drain pipe or soil pipe

150mm

H.

 From an internal or external corner or to a boundary alongside the terminal

300mm

I.

 Above ground, roof or balcony level

300mm

J.

 From a surface or a boundary facing the terminal

600mm

K.

 From a terminal facing the terminal

1200mm

L.

 From an opening in the car port into the building

1200mm

M.

 Vertically from a terminal on the same wall

1500mm

N.

 Horizontally from a terminal on the same wall

300mm

CONCENTRIC ROOF TERMINAL POSITIONS

Directly below an opening, air brick, windows, etc.

300mm

Below plastic/painted gutters

500mm*

Below painted surface

500mm*

Below eaves or balcony

500mm

From wall

1000mm

Below Velux window

2000mm

Above or side of Velux window

600mm

DOMESTIC BOILERS (UP TO 70kW)

BS5440

   

 

 Flues and ventilation for gas appliances of rated input not exceeding  

70 kW net (1st, 2nd and 3rd family gases). Specification for the installation and    

 

maintenance of ventilation provision for gas appliances. In I.E refer to I.S. 813.

Flue Termination Position

Due to the high efficiency of these boilers pluming will occur. For this reason vertical termination is 

recommended, and in any case, terminal positions which could cause problems should where possible be avoided.
Particular care should be taken in the case of large multiple boiler installations, and complying with the 

requirements of the Clean Air Act. The information below is extracted from BS. 5440 Pt. 1 and is for boilers with 

heat inputs not exceeding 70kW nett, and the latest Building Regulation Part J. Detailed reference should still be 

made to these standards. In IE refer to I.S. 813:2002.

* May be reduced to 300mm if a shield fitted. (1) An opening here means an openable element, such as a openable window, or a fixed opening such as an air vent. However, 

in addition, the outlet should not be nearer than 150mm (fanned draught) to an opening into the building fabric formed for the purpose of accommodating a built in 

element, such as a window frame.

Summary of Contents for EVOMAX 2 Series

Page 1: ...1 idealheating com EVOMAX 2 CONDENSING BOILER PRODUCT FLUE GUIDE H E A T I N G idealheating com welcome to our ideology Commercial Industrial Heating Product of the Year 2020...

Page 2: ...its Hull manufacturing plant and offices since 1906 Ideal is one of the few true British manufacturers left in the heating industry Your phone or tablet can let you appreciate our Condensing Boiler ra...

Page 3: ...5 year warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Heating Terms and conditions available at idealheating com 5 DOWNLOAD...

Page 4: ...warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Heating Terms and conditions available at idealheating com 1 3 4 5 7 6 8 9...

Page 5: ...Fuse Rating A 4 0 Power Consumption W 81 138 82 149 187 243 240 IP Rating IPX4D Nominal Flue Size concentric mm 80 125 100 150 Condensate Drain mm 25 Water Content l 3 0 5 0 7 0 9 2 Dry Weight Kg 47 5...

Page 6: ...perature differentials SOURCING The condensing boiler must be manufactured or finally assembled in the United Kingdom CASCADE The boiler must be configurable up to 6 boilers max 900kW in cascade using...

Page 7: ...ilers A Low Height Inline cascade can be for up to 4 boilers 1 Standard Height Frame required for each boiler in the cascade 1 pump required for each boiler in the cascade The wide range of options av...

Page 8: ...394 DN65 209395 DN80 219552 DN100 219553 DN150 219554 Magnetic Low Loss Mixing Header MLLH DN50 222191 DN65 222192 DN80 222193 DN100 222194 Plate Heat Exchanger Up to 60kW total output DN50 222219 Up...

Page 9: ...0 1950 to top of Frame 1918 to top boiler 300 650 1100 25 1480 25 530 850 574 120kW 560 456 664 150kW 212 200 380 2 BSP Female Gas Connection 1950 to top of Frame 1918 to top boiler 300 650 1650 25 25...

Page 10: ...0 6 x Evomax 2 boilers 120 150kW with LLH separation UIN DN FLANGE SIZE SUITABLE FOR 221127 DN50 1 x Evomax 2 boilers 30 150kW with PHEX or M LLH separation UIN DN FLANGE SIZE SUITABLE FOR 221128 DN65...

Page 11: ...EXCHANGER UP TO 60KW TOTAL OUTPUT PLATE HEAT EXCHANGER Covering outputs of 60 150 300 450 600 750 and 900kW Brazed Plate Heat Exchangers ensure optimum heat transfer efficiency and low resistance with...

Page 12: ...300 470 466 UIN DN FLANGE SIZE 222223 DN50 222225 DN80 222995 DN100 UIN DN FLANGE SIZE 222226 DN80 222996 DN100 330 709 376 632 519 UP TO 600KW TOTAL OUTPUT PLATE HEAT EXCHANGER UP TO 750KW TOTAL OUT...

Page 13: ...number of kits required LOW LOSS HEADER STANDARD HEIGHT INSULATION STARTER KIT STANDARD HEIGHT INSULATION CONTINUATION KIT STANDARD HEIGHT INSULATION CONTINUATION KIT DN100 STANDARD HEIGHT IN LINE HE...

Page 14: ...er Kit 1 1 1 UIN DESCRIPTION 1 BOILER CASCADE 2 BOILER CASCADE 3 BOILER CASCADE 4 BOILER CASCADE 223032 Low Height Insulation Starter Kit DN50 1 223035 Low Height Insulation Starter Kit DN65 1 223038...

Page 15: ...his schematic is an illustration of a hydraulic arrangement for discussion and reference use only The schematic may not accurately describe the actual arrangement required in order for the system to o...

Page 16: ...30 EVOMAX 2 FLUE OPTIONS 31 idealcommercialboilers com...

Page 17: ...elbow Terminal Locking collars x2 Wall plates x2 CONTENTS Terminal Locking Collar Finishing plates x2 Bracket To comply with CE certification Evomax boilers must be fitted with Ideal concentric flues...

Page 18: ...261 Extension Kit 100 150 213262 Pitched Weather Collar 80 125 152609 Pitched Weather Collar 100 150 152610 Flat Weather Collar 80 125 152611 Flat Weather Collar 100 150 152612 90 Elbow 80 125 single...

Page 19: ...imum pressure drop allowed in the flue for that boiler The maximum pressure drop allowed in the flue is given below PERMISSIBLE FLUE LENGTH The maximum permissible flue lengths for each model are show...

Page 20: ...r installations up to 600kW Type B23 flue Designed specifically to work efficiently with Evomax 2 boilers with commissioning simply completed by selecting Multiline flue from the installer set up menu...

Page 21: ...eter extension tube D 90 degree elbow E Flue terminal end F External wall plate G Internal wall plate H Wall bracket Note The 100 150mm Plume Kit system can also be used on Evomax 80 80P 60 60P model...

Page 22: ...stream of heat exchanger Fan upstream of heat exchanger B open flue B1 appliance with a draught diverter B11 B12 B14 B13 B2 appliance without draught diverter B21 B22 B23 TYPE B22 TYPE B23 TYPE B11 T...

Page 23: ...creased The Act was an important milestone in the development of a legal framework to protect the environment Although smog is no longer an issue more recent editions of the Clean Air Act have maintai...

Page 24: ...ement The approved documents offer guidance on how to comply and are not legally binding unless the manufacturer of the appliance stipulates them in the installation manual It is prudent however to fo...

Page 25: ...rs instructions NOTES 1 It is most important that the correct concentration of the water treatment products is maintained in accordance with the manufacturers instructions 2 If the boiler is installed...

Page 26: ...10 410 610 155 205 305 Low level 310 410 610 155 205 305 620 820 1220 310 410 610 CONCENTRIC WALL TERMINAL POSITIONS MINIMUM SPACING A Below an opening 1 300mm B Above an opening 1 300mm C Horizontall...

Page 27: ...y 230V AC 50 60 Hz 0 8amps Alarm contact NC 4 Amps resistive Overheat protection 130 C Tank Capacity 2 0 Litres Maximum vertical head 4 5m Maximum horizontal length 30m IDEAL COMMERCIAL BOILERS CONDEN...

Page 28: ...icated national service team delivering help and advice to you and your customers throughout the year BOILER TRAINING Our comprehensive one day courses can be mixed and matched for individual installa...

Page 29: ...ry rights of the consumer are not affected PLEASE NOTE The information in this brochure was correct at the time of going to print Ideal Heating reserve the right to make any modifications to product s...

Reviews: