CONDENSATE PUMPS
The condensate pump is designed to collect and remove condensate and can be used
with high efficiency condensing boilers.
TECHNICAL INFORMATION
Maximum flow rate
440 litres/hour
Electrical supply
230V AC / 50-60 Hz 0.8amps
Alarm contact
NC 4 Amps resistive
Overheat protection
130˚C
Tank Capacity
2.0 Litres
Maximum vertical head
4.5m
Maximum horizontal length
30m
IDEAL COMMERCIAL BOILERS - CONDENSATE PUMP COMPATIBILITY
BOILER
COMPATIBLE
EVOMAX 2 - 30 - 150kW
IMAX XTRA - 80 - 280kW
IMAX XTRA EL - 320 - 1240kW
EVOMOD - 250 - 1000kW
EVOJET - 150 - 1450kW
TERMINATION TO DRAIN / GULLEY
SEE INSTALLATION MANUAL FOR FULL INSTRUCTIONS
AND SYSTEM OPTIONS