EVOMAX 2 30 - 150kW (Natural Gas & LPG)

*Optional kit available on 60kW and 80kW models for 100/150mm flue

PERFORMANCE DATA

EVOMAX 2 30 - 150kW (Natural Gas)

EVOMAX 2 30 - 120kW (LPG)

MODEL

30

40

60

80

100

120

150

Boiler Output (non-condensing) 

Mean 70°C

Max

kW

30

40

60

80

100

120

150

Min

kW

6

8

12

16

20

24

30

Boiler Output (condensing) Mean 

40°C

Max

kW

31.5

42.0

63.5

84.4

103.9

124.7

158

Min

kW

6.5

8.5

12.7

17.2

21.6

26.0

32.5

Boiler Input Max Rate

Net

kW

30.4

40.5

60.8

82.0

102.4

122.9

153.7

Gross

kW

33.7

44.9

67.4

90.9

113.6

136.4

170.5

Boiler Input Min Rate

Net

kW

6.1

8.1

12.2

16.4

20.5

24.6

30.7

Gross

kW

6.7

9.0

13.5

18.2

22.7

27.3

34.1

Gas Rate

Max rate

m

³

/hr

3.2

4.3

6.4

8.7

10.8

13.0

16.2

Flue Gas Flow Rate

Max Rate

m

³

/hr

41.30

54.05

80.65

110.10

140.50

173.33

210.70

CO

 (

±

0.5%)

Max Rate

%

9.76

10.20

9.40

9.30

9.40

9.62

9.44

Min Rate

%

8.56

8.60

8.60

8.70

8.60

8.98

8.51

NOx with O

 = 0% (gross)

Weighted

mg/kWh

34.1

33.2

35.2

34.9

34.8

33.9

35.7

Efficiency

Seasonal

%

96.7

96.2

96.4

97.2

96.7

96.6

96.7

*SEDBUK 

2009

%

89.6

89.3

89.4

n/a

n/a

n/a

n/a

Operating Temperature

Max

˚C

85

MODEL

30/30P

40/40P

60/60P

80/80P

100/100P

120/120P

150

Gas Supply

2H - G20 - 20mbar / 3P - G31 - 37mbar

Gas Supply  

Connection

¾

Flow Connection

G1 

¼

Return Connection

G1 

¼

Max Pressure  

(sealed system)

Bar 

(psi)

6

Maximum Static Head

m

61

Electricity Supply

230V - 50Hz

Fuse Rating

A

4.0

Power Consumption

W

81

138

82

149

187

243

240

IP Rating

IPX4D

Nominal Flue Size 

(concentric)

mm

80/125*

100/150

Condensate Drain

mm

25

Water Content

l

3.0

5.0

7.0

9.2

Dry Weight

Kg

47.5

57.5

73

81

Weighted Power Level

dBA

55.2

57.7

59

59.9

62

62

59

BOILER

EVOMAX 2

Remote indication (run & alarm)

Hours run

BMS (0-10v) operation

Pump overrun

Large backlit LCD controls,

including 5 line plain text 

display

Dynamic control menu set up

BOILER

EVOMAX 2

Multi boiler frame & header kits 

(see pages 16-19)

Varican Module Master Kit

Varican Module Slave Kit

Extension Module Kit

OPENTHERM Room Control Kit

Room Sensor Kit

Tank Sensor Kit

Outside Sensor Kit

Header Flow Tank Immersion Sensor Kit

Header Flow Tank Strap On Sensor Kit

Safety Interlock Kit

0-10V Pump Control Kit

Condensate Pump

MODEL

30P

40P

60P

80P

100P

120P

Boiler Output (non-condensing)

Mean 70°

Max

kW

30

40

60

80

100

120

Min

kW

6

8

12

16

20

24

Boiler Output (condensing) Mean 40°C

Max

kW

30.9

41.2

62.1

82.6

101.7

123.3

Min

kW

6.4

8.3

12.4

16.8

21.3

25.7

Boiler Input Max Rate

Net

kW

30.4

40.5

60.7

81.9

102.4

122.9

Gross

kW

33

44

66

88.9

111.2

133.4

Boiler Input Min Rate

Net

kW

6.1

8.1

12.0

16.2

20.5

24.6

Gross

kW

6.6

8.8

13.1

17.5

22.2

26.7

Gas Rate

Max rate

m

³

/hr

1.26

1.69

2.53

3.41

4.35

5.23

Flue Gas Flow Rate

Max Rate

m

³

/hr

44.09

61.68

88.66

121.57

153.60

183.81

CO

 (

±

0.5%)

Max Rate

%

10.9

11.2

11.4

11.4

10.8

11.2

Min Rate

%

10.3

9.7

10.2

10.8

10.1

10.1

NOx with O

 = 0% (gross)

Weighted

mg/kWh

52.3

64.4

67.7

63.2

65.3

41.6

Efficiency

Seasonal

%

97.2

96.7

96.9

97.7

96.7

96.6

*SEDBUK 

2009

%

90.6

90.3

90.5

n/a

n/a

n/a

Operating Temperature

Max

˚C

85

Summary of Contents for EVOMAX 2 Series

Page 1: ...1 idealheating com EVOMAX 2 CONDENSING BOILER PRODUCT FLUE GUIDE H E A T I N G idealheating com welcome to our ideology Commercial Industrial Heating Product of the Year 2020...

Page 2: ...its Hull manufacturing plant and offices since 1906 Ideal is one of the few true British manufacturers left in the heating industry Your phone or tablet can let you appreciate our Condensing Boiler ra...

Page 3: ...5 year warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Heating Terms and conditions available at idealheating com 5 DOWNLOAD...

Page 4: ...warranty subject to Terms and Conditions 5 years parts and labour warranty available subject to being commissioned by Ideal Heating Terms and conditions available at idealheating com 1 3 4 5 7 6 8 9...

Page 5: ...Fuse Rating A 4 0 Power Consumption W 81 138 82 149 187 243 240 IP Rating IPX4D Nominal Flue Size concentric mm 80 125 100 150 Condensate Drain mm 25 Water Content l 3 0 5 0 7 0 9 2 Dry Weight Kg 47 5...

Page 6: ...perature differentials SOURCING The condensing boiler must be manufactured or finally assembled in the United Kingdom CASCADE The boiler must be configurable up to 6 boilers max 900kW in cascade using...

Page 7: ...ilers A Low Height Inline cascade can be for up to 4 boilers 1 Standard Height Frame required for each boiler in the cascade 1 pump required for each boiler in the cascade The wide range of options av...

Page 8: ...394 DN65 209395 DN80 219552 DN100 219553 DN150 219554 Magnetic Low Loss Mixing Header MLLH DN50 222191 DN65 222192 DN80 222193 DN100 222194 Plate Heat Exchanger Up to 60kW total output DN50 222219 Up...

Page 9: ...0 1950 to top of Frame 1918 to top boiler 300 650 1100 25 1480 25 530 850 574 120kW 560 456 664 150kW 212 200 380 2 BSP Female Gas Connection 1950 to top of Frame 1918 to top boiler 300 650 1650 25 25...

Page 10: ...0 6 x Evomax 2 boilers 120 150kW with LLH separation UIN DN FLANGE SIZE SUITABLE FOR 221127 DN50 1 x Evomax 2 boilers 30 150kW with PHEX or M LLH separation UIN DN FLANGE SIZE SUITABLE FOR 221128 DN65...

Page 11: ...EXCHANGER UP TO 60KW TOTAL OUTPUT PLATE HEAT EXCHANGER Covering outputs of 60 150 300 450 600 750 and 900kW Brazed Plate Heat Exchangers ensure optimum heat transfer efficiency and low resistance with...

Page 12: ...300 470 466 UIN DN FLANGE SIZE 222223 DN50 222225 DN80 222995 DN100 UIN DN FLANGE SIZE 222226 DN80 222996 DN100 330 709 376 632 519 UP TO 600KW TOTAL OUTPUT PLATE HEAT EXCHANGER UP TO 750KW TOTAL OUT...

Page 13: ...number of kits required LOW LOSS HEADER STANDARD HEIGHT INSULATION STARTER KIT STANDARD HEIGHT INSULATION CONTINUATION KIT STANDARD HEIGHT INSULATION CONTINUATION KIT DN100 STANDARD HEIGHT IN LINE HE...

Page 14: ...er Kit 1 1 1 UIN DESCRIPTION 1 BOILER CASCADE 2 BOILER CASCADE 3 BOILER CASCADE 4 BOILER CASCADE 223032 Low Height Insulation Starter Kit DN50 1 223035 Low Height Insulation Starter Kit DN65 1 223038...

Page 15: ...his schematic is an illustration of a hydraulic arrangement for discussion and reference use only The schematic may not accurately describe the actual arrangement required in order for the system to o...

Page 16: ...30 EVOMAX 2 FLUE OPTIONS 31 idealcommercialboilers com...

Page 17: ...elbow Terminal Locking collars x2 Wall plates x2 CONTENTS Terminal Locking Collar Finishing plates x2 Bracket To comply with CE certification Evomax boilers must be fitted with Ideal concentric flues...

Page 18: ...261 Extension Kit 100 150 213262 Pitched Weather Collar 80 125 152609 Pitched Weather Collar 100 150 152610 Flat Weather Collar 80 125 152611 Flat Weather Collar 100 150 152612 90 Elbow 80 125 single...

Page 19: ...imum pressure drop allowed in the flue for that boiler The maximum pressure drop allowed in the flue is given below PERMISSIBLE FLUE LENGTH The maximum permissible flue lengths for each model are show...

Page 20: ...r installations up to 600kW Type B23 flue Designed specifically to work efficiently with Evomax 2 boilers with commissioning simply completed by selecting Multiline flue from the installer set up menu...

Page 21: ...eter extension tube D 90 degree elbow E Flue terminal end F External wall plate G Internal wall plate H Wall bracket Note The 100 150mm Plume Kit system can also be used on Evomax 80 80P 60 60P model...

Page 22: ...stream of heat exchanger Fan upstream of heat exchanger B open flue B1 appliance with a draught diverter B11 B12 B14 B13 B2 appliance without draught diverter B21 B22 B23 TYPE B22 TYPE B23 TYPE B11 T...

Page 23: ...creased The Act was an important milestone in the development of a legal framework to protect the environment Although smog is no longer an issue more recent editions of the Clean Air Act have maintai...

Page 24: ...ement The approved documents offer guidance on how to comply and are not legally binding unless the manufacturer of the appliance stipulates them in the installation manual It is prudent however to fo...

Page 25: ...rs instructions NOTES 1 It is most important that the correct concentration of the water treatment products is maintained in accordance with the manufacturers instructions 2 If the boiler is installed...

Page 26: ...10 410 610 155 205 305 Low level 310 410 610 155 205 305 620 820 1220 310 410 610 CONCENTRIC WALL TERMINAL POSITIONS MINIMUM SPACING A Below an opening 1 300mm B Above an opening 1 300mm C Horizontall...

Page 27: ...y 230V AC 50 60 Hz 0 8amps Alarm contact NC 4 Amps resistive Overheat protection 130 C Tank Capacity 2 0 Litres Maximum vertical head 4 5m Maximum horizontal length 30m IDEAL COMMERCIAL BOILERS CONDEN...

Page 28: ...icated national service team delivering help and advice to you and your customers throughout the year BOILER TRAINING Our comprehensive one day courses can be mixed and matched for individual installa...

Page 29: ...ry rights of the consumer are not affected PLEASE NOTE The information in this brochure was correct at the time of going to print Ideal Heating reserve the right to make any modifications to product s...

Reviews: