Subject to technical changes | Valid as of January 2022
30
TECHNOLOGY
CALEO COLD/NEUTRAL
02
2.4.1. Electrical information
The units are electrically fully equipped and installed (due to special construction depending on the order specification, the product
may be prepared for customer-side controller/electrics).
The cooling zone controller is completely set and ready for operation. After completion of the installation, check parameter
H11 (calibration of return air sensor). The cooling zone controller must be set-up by an authorised specialist according
to the enclosed programming guide.
NOTE
Danger from electrical voltage on live components.
The electrical connection must be carried out by an authorised specialist
and comply with the applicable standards, regulations and safety regulations.
Danger from electrical voltage on live components
The mains voltage and frequency must match the values given on the rating plate. It is not permitted to connect to any other
voltage, type of current or frequency. The relevant, local, safety regulations must be observed.
DANGER
DANGER
Self-contained units are delivered with a 1.5-meter-long power cord with an earthing contact plug as a standard feature. It is connected
to an AC power grid with a nominal AC voltage and frequency of 230 volts 50 Hz (country dependent with 115V 60Hz, 120V 60Hz,
220-240V 50-60Hz). The electrical supply line must be protected with a 16 A fuse (trip characteristic “C”).
If a plug connection is used for the mains connection, then the power outlet must be easily accessible to be able to disconnect the
unit from the power grid if need be (cleaning, maintenance work). If direct wiring is used, then a means of disconnecting the unit
from the power grid must be provided.
Connection of the unit
Possibility of disconnection from the power grid
Summary of Contents for CALEO COLD
Page 1: ...Operating Manual CALEO COLD NEUTRAL 22A Translation of the original ...
Page 2: ...Subject to technical changes Valid as of January 2022 2 ...
Page 41: ...Subject to technical changes Valid as of January 2022 41 NOTES CALEO COLD NEUTRAL ...
Page 53: ...Subject to technical changes Valid as of January 2022 53 NOTES CALEO COLD NEUTRAL ...