ICP DAS, ZT-2570/ZT-2571 User Manual, Version 1.3
Page 30
Copyright @ 2013 by ICP DAS Co., Ltd. All Rights Reserved.
4.5
Configuration Example
The following configurations are common examples of various application
scenarios. Please refer the “4.1
Introduction of Configurations
” for detailed
explanation of each configurations.
ZT-2550
ZT-2570
ZT-20xx
ZT-2551
ZT-2571
Note
Pan ID
00 00
00 00
Group identity should be the same
Node ID
00 00
00 01 ~ 3F FF
Node identity cannot be repeated
RF Channel
E
E
Radio frequency should be the same
RS-232/RS-485
Baud Rate
Data Format
Receive Interval
115200
N,8,1
3.5 character
time
9600
E,8,1
3.5 character
time
※
User-configurable
The wired-communication are
independent to each ZT devices, so the
baud rate and data format are also
independent on both side
Ethernet
Server/Client
TCP Server
TCP Client
IP
Port
10.1
.0.70
502
192.168
.0.70
502
※
User-configurable
The wired-communication are
independent to each ZT devices, so the
ZT-2570 and ZT-2571 are not in the
same LAN.
<Reminding >
Please confirm the TCP client is disabled if there is not any TCP server
connected
–
otherwise the ZT device will try to establish TCP connection
continuously, which results the communication blocking.