ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Page 106
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
00584
to 7:
0: Disable
1: Enable
00609
~
00616
Enables or disables the low alarm for channels 0
to 7:
0: Disable
1: Enable
R/W
00641
~
00648
The high alarm mode for channels 0 to 7:
0: Momentary
1: Latch
R/W
00673
~
00680
The low alarm mode for channels 0 to 7:
0: Momentary
1: Latch
R/W
00705
~
00712
The status of the high alarms for channels 0 to 7
R/W
00737
~
00744
The status of the low alarms for channels 0 to 7
R/W
10129
~
10136
The under range status of channels 0 to 7
(supports types 0x7 and 0x1A only)
R
30001
~
30008
The analog input value for channels 0 to 7
R
30513
~
30520
The high latch value for channels 0 to 7
R
30545
~
30552
The low latch value for channels 0 to 7
R
40257
~
40264
The type code for channels 0 to 7
R/W
40481
The Firmware Version (Low Word)
R
40482
The Firmware Version (Ligh Word)
R
40483
The Module Name (Low Word)
R
40484
The Module Name (High Word)
R
40485
The Module Address. Valid Range: 1
~
247
R
40486
The Baud Rate:
Bits 5:0 Baud Rate. Always set to 0x0A
R