6.2.23
~AAO(Name)
Description
This command is used to set the name of a specified module.
Syntax
~
AAO(Name)[CHECKSUM](CR)
~
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
O
The command to set the name of the module
(Name) The new name of the module (Max. 8 characters)
Response
Valid Command
!AA[CHECKSUM](CR)
Invalid Command
?AA[CHECKSUM](CR)
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples
Command
~
03OZT-2017
Response !03
Sets the name of module 03 to “ZT-2017” and returns a response indicating that
the command was successful.
Command $03M
Response !03ZT-2017
Reads the name of module 03 and returns a response indicating that the
command was successful, with the name “ZT-2017”.
※Related Commands: $AAM