ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Page 117
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
6.3.10
70 (0x46) Reading/Writing the Module
Settings
Description
This function code is used to read the configuration settings from the
module or to change the settings for the module. The following
sub-function codes are supported.
Sub-function
Code
Description
Section
00 (0x00)
Reads the Name of the Module
A.1
04 (0x04)
Sets the Address of the Module
A.2
07 (0x07)
Reads the Type Code
A.3
08 (0x08)
Sets the Type Code
A.4
32 (0x20)
Reads the Firmware Version
A.5
37 (0x25)
Reads the Enabled/Disabled
Status of a Specific Channel
A.6
38 (0x26)
Sets a Specific Channel to
Enabled/Disabled
A.7
41 (0x29)
Reads the Miscellaneous Settings
A.8
42 (0x2A)
Writes the Miscellaneous Settings
A.9
If the module does not support the sub-function code specified in the message,
then it will response as foolows:
Error Response
Byte Description
Length Value
00
Address
1
1 to 247