ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Page 104
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
6.3
Modbus RTU Protocol Command set
The Modbus Protocol was developed by Modicon Inc., and was originally
designed for Modicon controllers. Detailed information regarding the
Modbus RTU Protocol can be found at:
Modbus RTU Command Format
Field
1
Field
2
Field
3
Field
4
~
n
Field
n+1
~
n+2
Module
Address
Function
Code
Sub
Function
Configuration
Field
CRC16
Function Code Description
0x04
Reads the input channels
0x46
Reads/writes the module settings
Examples:
A.
To read the analog input value for module 01, the following command
should be sent:
01 04 00 00 00 08 F1 CC
B.
To read the name of the module, the following command should be
sent:
01 46 00 12 60