ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Page 130
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
A.9
42(0x2A) Writing the Miscellaneous Settings
Description
This sub-function code is used to configure the miscellaneous settings
for a module.
Request
Byte Description
Length Value
00
Address
1
1 to 247
01
Function Code
1
0x46
02
Sub-function
Code
1
0x2A
03
Miscellaneous
Settings
1
The data format. See Section 1.8 for details.
Response
Byte Description
Length Value
00
Address
1
1 to 247
01
Function Code
1
0x46
02
Sub-function
Code
1
0x2A
03
Miscellaneous
Settings
1
0: OK
Others: Error
Error Response
Byte Description
Length Value
00
Address
1
1 to 247
01
Function Code
1
0xC6
02
Exception Code
1
Refer to the Modbus standard for more
details