3.3 03 (0x03) Read Output Channels
This function code is used to read the analog output values of a
module.
Request
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x03
02 ~ 03 Starting channel 2 Bytes 0x0000 ~ 0x0001 for M-7022
0x0000 ~ 0x0003 for M-7024
0x0000 ~ 0x0003 for M-7024L
0x0000 ~ 0x0003 for M-7024R
0x0000 ~ 0x0003 for M-7024U
0x0000 ~ 0x0007 for M-7028
04 ~ 05 Number of
output channels
(N)
2 Bytes 0x0001 ~ 0x0002 for M-7022
0x0001 ~ 0x0004 for M-7024
0x0001 ~ 0x0004 for M-7024L
0x0001 ~ 0x0004 for M-7024R
0x0001 ~ 0x0004 for M-7024U
0x0001 ~ 0x0008 for M-7028
Response
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x03
02
Byte count
1 Byte N x 2
03 ~
Data of output
channels
N x 2
Bytes
Data in the specified data format
Error Response
00
Address
1 Byte 1 ~ 247
01
Function code
1 Byte 0x83
02
Exception code
1 Byte 02: starting channel out of range
03: (starting c number of
output channels) out of range,
incorrect number of bytes received