![ICP DAS USA I-7021 User Manual Download Page 37](http://html1.mh-extra.com/html/icp-das-usa/i-7021/i-7021_user-manual_3685406037.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
37
Data Format Setting (FF)
7
6
5
4
3
2
1
0
0
CS
SR
DF
Key
Description
DF
Data format
00: Engineering unit
01
*
: % of FSR (full scale range)
10
*
: 2’s complement hexadecimal
Note: the data format 01 and 10 are only
available to the I-7021/21P, I-7022, M-7022,
M-7024U and M-7028
SR
Slew rate for I-7021, I-7021P, I-7024, I-7024R,
M-7024, M-7024L and M-7024R
V/s
mA/s
V/s
mA/s
0000
immediate
1000
8.0
16.0
0001
0.0625 0.125
1001
16.0
32.0
0010
0.125
0.25
1010
32.0
64.0
0011
0.25
0.5
1011
64.0
128.0
0100
0.5
1.0
1100
128.0
256.0
0101
1.0
2.0
1101
256.0
512.0
0110
2.0
4.0
1110
512.0
1024.0
0111
4.0
8.0
1111
1024.0 2048.0
Note: the setting 1111 is for I-7024, I-7024R,
M-7024, M-7024L and M-7024R only
0 for I-7022, M-7022, M-7024U and M-7028
CS
Checksum setting
0: Disabled
1: Enabled
Summary of Contents for I-7021
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...