![ICP DAS USA I-7021 User Manual Download Page 163](http://html1.mh-extra.com/html/icp-das-usa/i-7021/i-7021_user-manual_3685406163.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
163
Address Description
Attribute
40488
Modbus response delay time in ms,
valid range: 0 ~ 30
R/W
40489
Host watchdog timeout value, 0 ~ 255,
in 0.1s
R/W
40492
Host watchdog timeout count, write 0
to clear
R/W
00257
Protocol, 0: DCON, 1: Modbus RTU R/W
00258
Modbus Protocol, 0:RTU. 1:ASCII
R/W
00260
Modbus host watchdog mode
0: same as I-7000
1: can use AO and DO command to
clear host watchdog timeout status
R/W
00261
1: enable, 0: disable host watchdog
R/W
00269
Modbus data format, 0: hex, 1:
engineering
R/W
00270
Host watch dog timeout status, write 1
to clear host watch dog timeout status
R/W
00273
Reset status, 1: first read after
powered on, 0: not the first read after
powered on
R
Output Types
Type Code Output Range
Data Format
Max
Min
0
0 ~ 20 mA
Engineering
20000
0
Hexadecimal
0FFFh
0000h
1
4 ~ 20 mA
Engineering
20000
4000
Hexadecimal
0FFFh
0000h
2
0 ~ 10 V
Engineering
10000
0
Hexadecimal
0FFFh
0000h
4
0 ~ 5 V
Engineering
5000
0
Hexadecimal
0FFFh
0000h
Notes: Engineering data format and type code 4 are supported by
firmware version B102 and later.
Summary of Contents for I-7021
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...