I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
137
2.43 ~AA5N
Description:
Sets the current analog output value as the safe analog
output value for a specified channel of a module.
Syntax:
~AA5N[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be set (00 to FF)
5
Command to set the safe analog output value
N
The channel to be set, zero based
Response:
Valid command :
!AA[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: ~0151
Response: !01
Sets the safe analog output value of channel 1 of
module 01 and returns a valid response.
I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028