![ICP DAS USA I-7021 User Manual Download Page 76](http://html1.mh-extra.com/html/icp-das-usa/i-7021/i-7021_user-manual_3685406076.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
76
2.11 $AA3NVV
Description:
Adjusts the analog output of a specified channel for
calibration.
Syntax:
$AA3NVV[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be adjusted (00 to FF)
3
Command to adjust the analog output
N
The channel to be adjusted, zero based
VV
A two-digit 2’s complement hexadecimal value
to adjust the analog output. The value of 00 to
5F is to increase 0 to 95 counts and FF to A1 is
to decrease 1 to 95 counts, where each count is
about 4.88uA or 2.44mV for I-7022, M-7022
and M-7028, 2.44uA or 1.22mV for I-7024/24R
and M-7024/24R, 0.61uA or 0.30mA for
M-7024U.
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028