![ICP DAS USA I-7021 User Manual Download Page 111](http://html1.mh-extra.com/html/icp-das-usa/i-7021/i-7021_user-manual_3685406111.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
111
2.29 $AAM
Description:
Reads the name of a module.
Syntax:
$AAM[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
M
Command to read the module name
Response:
Valid command:
!AA(Data)[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
(Name) Name string of the module
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: $01M
Response: !017021
Reads the module name of module 01 and returns the
name “7021”.
Related Commands:
Section 2.33 ~AAO(Name)
I-7021, I-7021P, I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028
Summary of Contents for I-7021
Page 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Page 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Page 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Page 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...