![ICP DAS USA I-7021 User Manual Download Page 39](http://html1.mh-extra.com/html/icp-das-usa/i-7021/i-7021_user-manual_3685406039.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
39
Analog Output Type and Data Format Table for
I-7024, I-7024R, M-7024, M-7024L and M-7024R
Type Code Output Range Data Format
Max.
Min.
30
0 ~ +20 mA
Engineering unit +20.000 +00.000
31
+4 ~ +20 mA Engineering unit +20.000 +04.000
32
0 ~ +10 V
Engineering unit +10.000 +00.000
33
-10 ~ +10 V
Engineering unit +10.000 -10.000
34
0 ~ +5 V
Engineering unit +05.000 +00.000
35
-5 V ~ +5 V
Engineering unit +05.000 -05.000
Analog Output Type and Data Format Table for
M-7024U and M-7028
Type Code Output Range Data Format
Max.
Min.
0
0 ~ +20 mA
Engineering unit +20.000 +00.000
% of FSR
+100.00 +000.00
2’s comp HEX
FFFF
0000
1
+4 ~ +20 mA
Engineering unit +20.000 +04.000
% of FSR
+100.00 +000.00
2’s comp HEX
FFFF
0000
2
0 ~ +10 V
Engineering unit +10.000 +00.000
% of FSR
+100.00 +000.00
2’s comp HEX
FFFF
0000
3
-10 ~ +10V
Engineering unit +10.000 -10.000
% of FSR
+100.00 -100.00
2’s comp HEX
7FFF
8000
4
0 ~ +5 V
Engineering unit +05.000 +00.000
% of FSR
+100.00 +000.00
2’s comp HEX
FFFF
0000
5
-5 ~ +5 V
Engineering unit +05.000 -05.000
% of FSR
+100.00 -100.00
2’s comp HEX
7FFF
8000
Summary of Contents for I-7021