5. Testing the Expansion Valve
The expansion valve (TXV) is designed to modulate the
flow of refrigerant, depending upon the needs of the
evaporator.
Extremely thin ice at the evaporator outlet could be a sign
that the machine is undercharged or that the TXV is
starving the evaporator for refrigerant.
Similarly, extremely thin ice at the evaporator inlet could
be a sign that the machine is overcharged or that the TXV
is flooding the evaporator with refrigerant.
To test the TXV, remove the sensing bulb from the suction
line, just after the evaporator outlet. While watching the
low-side on the manifold gauge set, hold the bulb tightly
in you hand and watch to see if the low-side pressure
begins to rise, indicating more refrigerant is entering the
evaporator.
Next, place the bulb in a cup of ice water and watch to
see if the low-side pressure drops again, indicating less
refrigerant is entering the evaporator.
81
Summary of Contents for IM Series
Page 1: ...Revision Date 1 24 22 IM Series Air Water Remote Ice Machines Technician s Handbook ...
Page 2: ......
Page 3: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 9: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 15: ...THIS PAGE INTENTIONALLY LEFT BLANK 14 ...
Page 17: ...How to Read a Serial Number Full Serial Number 16 ...
Page 35: ...THIS PAGE INTENTIONALL Y LEFT BLANK 34 ...
Page 48: ...Flexible Numeric Display FND Functions 47 ...
Page 93: ...THIS PAGE INTENTIONALLY LEFT BLANK 92 ...
Page 106: ...Testing the water level sensor Before S N Starting With VC 105 ...
Page 134: ...SERVICE REMOTE RECOVERY EVACUATION CONNECTIONS 133 ...
Page 145: ...THIS PAGE INTENTIONALLY LEFT BLANK 144 ...
Page 155: ...THIS PAGE INTENTIONALLY LEFT BLANK 154 ...
Page 157: ...Wiring Diagram 156 ...
Page 158: ...PCB Layout 157 ...
Page 159: ...PCB Dip Switches 158 ...
Page 161: ...SPACE FOR TECHNICIAN S NOTES ...
Page 162: ...SPACE FOR TECHNICIAN S NOTES ...
Page 163: ...SPACE FOR TECHNICIAN S NOTES ...
Page 164: ...SPACE FOR TECHNICIAN S NOTES ...
Page 165: ......