Contamination Cleanup Chart
Symptoms/Findings
Required Cleanup Procedure
No symptoms or suspicion
of contamination.
Normal evacuation/
recharging procedure
Moisture/Air Contamination
symptoms.
Refrigeration system open to
atmosphere for longer than
15 minutes. Refrigeration test
kit and/or acid oil test shows
contamination.
Leak in water cooled
condenser.
No burnout deposits in open
compressor lines.
Mild contamination
cleanup procedure
Mild Compressor Burnout
symptoms.
Oil appears clean but smells
acrid.
Refrigeration test kit or acid
oil test shows harmful acid
content.
No burnout deposits in
open compressor lines.
Mild contamination
cleanup procedure
Severe Compressor Burnout
symptoms.
Oil is discolored, acidic, and
smells acrid.
Burnout deposits found in
the compressor, lines, and
other components.
Severe contamination
cleanup procedure
137
Summary of Contents for IM Series
Page 1: ...Revision Date 1 24 22 IM Series Air Water Remote Ice Machines Technician s Handbook ...
Page 2: ......
Page 3: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 9: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 15: ...THIS PAGE INTENTIONALLY LEFT BLANK 14 ...
Page 17: ...How to Read a Serial Number Full Serial Number 16 ...
Page 35: ...THIS PAGE INTENTIONALL Y LEFT BLANK 34 ...
Page 48: ...Flexible Numeric Display FND Functions 47 ...
Page 93: ...THIS PAGE INTENTIONALLY LEFT BLANK 92 ...
Page 106: ...Testing the water level sensor Before S N Starting With VC 105 ...
Page 134: ...SERVICE REMOTE RECOVERY EVACUATION CONNECTIONS 133 ...
Page 145: ...THIS PAGE INTENTIONALLY LEFT BLANK 144 ...
Page 155: ...THIS PAGE INTENTIONALLY LEFT BLANK 154 ...
Page 157: ...Wiring Diagram 156 ...
Page 158: ...PCB Layout 157 ...
Page 159: ...PCB Dip Switches 158 ...
Page 161: ...SPACE FOR TECHNICIAN S NOTES ...
Page 162: ...SPACE FOR TECHNICIAN S NOTES ...
Page 163: ...SPACE FOR TECHNICIAN S NOTES ...
Page 164: ...SPACE FOR TECHNICIAN S NOTES ...
Page 165: ......