Iceco 80LJ SERIES Installation Instructions Manual Download Page 35

35

important that the airflow is not reduced
to maximize system performance and
life. Always verify that the systems
airflow is not impaired by the filtering
system that has been installed, by
performing a temperature rise and
temperature drop test.

Keep the air filters clean at all times.
Vacuum dirt from filter, wash with
detergent and water, air dry thoroughly
and reinstall.

See Table 8 and Figures 24, 25, 26, and
27 for proper filter sizes and locations.

1. 14”- 50,000 BTUH unit requires

removal of 3

1

/

2

” segment of filter and

frame to get proper width for a bottom
filter.

2. 21”-100,000 BTUH unit requires

removal of 3

1

/

2

” segment of filter and

frame to get proper width for a side
filter.

3. 24

1

/

2

”-125,000 and 150,000 BTUH

units require removal of 7” segment of
filter and frame to get proper width for
a side filter.

IMPORTANT:

Do not operate the

system without filters. A portion of the
dust entrained in the air may temporarily
lodge in the air duct runs and at the
supply registers. Any recirculated dust
particles will be heated and charred by
contact with the furnace heat
exchanger. This residue will soil
ceilings, walls, drapes, carpets, and
other household articles.

SYSTEM OPERATION
INFORMATION

Advise The Customer To:

1. Keep the air filters clean. The heating

system will operate better, more
efficiently and more economically.

2. Arrange the furniture and drapes so

that the supply air registers and the
return air grilles are unobstructed.

3. Close doors and windows. This will

reduce the heating load on the
system.

4. Avoid excessive use of kitchen &

bathroom exhaust fans.

5. Do not permit the heat generated by

television, lamps or radios to
influence the thermostat operation.

6 Except for the mounting platform,

keep all combustible articles three
feet from the furnace and vent
system.

7.

IMPORTANT: 

Replace all blower

doors and compartment covers after
servicing the furnace. Do not operate
the unit without all panels and doors
securely in place.

8. Proper operation of the system with

constant air circulation.

COMBUSTIBLE MATERIAL MUST
NOT BE PLACED ON OR AGAINST
THE FURNACE JACKET OR WITHIN
THE SPECIFIED CLEARANCES OF
THE VENT PIPE. THE AREA
AROUND THE FURNACE MUST BE
KEPT CLEAR AND FREE OF ALL
COMBUSTIBLE MATERIALS
INCLUDING GASOLINE AND OTHER
FLAMMABLE VAPORS AND
LIQUIDS. PLACEMENT OF
COMBUSTIBLE MATERIALS ON,
AGAINST OR AROUND THE
FURNACE JACKET CAN CAUSE AN
EXPLOSION OR FIRE RESULTING
IN PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
THE FURNACE OWNER SHOULD BE
CAUTIONED THAT THE FURNACE
AREA MUST NOT BE USED AS A
BROOM CLOSET OR FOR ANY
OTHER STORAGE PURPOSES.

ANNUAL INSPECTION

The furnace should operate for many
years without excessive scale build-up
in the flue passageways, however, it is
recommended that a qualified installer,
service agency, or the gas supplier
actually inspect the flue passageways,
the vent system and the main and pilot
burners for continued safe operation
paying particular attention to
deterioration from corrosion or other
sources.

HOLES IN THE VENT PIPE OR HEAT
EXCHANGER CAN CAUSE TOXIC
FUMES TO ENTER THE HOME
RESULTING IN CARBON
MONOXIDE POISONING OR DEATH.
THE VENT PIPE OR HEAT
EXCHANGER MUST BE REPLACED
IF THEY LEAK.

• IMPORTANT: 

It is recommended

that at the beginning of the heating
season and approximately midway
in the heating season a visual
inspection be made of the main
burner flames and pilot flame on
standing pilot models for the desired
flame appearance by a qualified
installer, service agency, or the gas
supplier.

• IMPORTANT: 

It is also

recommended that at the beginning
of the heating season, the flame
sensor on hot surface ignition
models be cleaned with steel wool
by a qualified installer, service
agency, or the gas supplier.

IMPORTANT: 

It is recommended

that an annual inspection and
cleaning of all furnace markings be
made to assure legibility. Attach a
replacement marking, which can be
obtained through the distributor, if
any are found to be illegible or
missing.

IMPORTANT: FOR Nox MODELS –

At the beginning of the heating season
a visual inspection of the Nox device
should be made to ensure they have
not become obstructed by insects
nests or anything else which may
effect performance.

REPLACEMENT PARTS

Contact your local distributor for a
complete parts list. See enclosed
sheet.

TROUBLESHOOTING

Refer to Figure 28 for determining
cause of unit problems.

WIRING DIAGRAM

Figures 29 and 30 are complete wiring
diagrams for the furnace and power
sources.

WARNING

!

WARNING

!

Summary of Contents for 80LJ SERIES

Page 1: ...CTIONS FOR UPFLOW UPFLOW HORIZONTAL AND DOWNFLOW INDUCED DRAFT GAS FURNACES 80PJ AND 80LJ SERIES PROPOSITION 65 THIS PRODUCT CONTAINS CHEMICALS INCLUDING CARBON MONOXIDE KNOWN TO THE STATE OF CALIFORN...

Page 2: ...furnace ground to electrical panel DC microamp A flame signal hot surface ignition units Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected...

Page 3: ...fects such as fiberglass insulation lead in brass and combustion products from natural gas All new equipment shipped for sale in California will have labels stating that the product contains and or pr...

Page 4: ...N PLACE SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RATING PLATE MARKING MEANS FOR PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55 F 13 C AND 80 F 27 C A...

Page 5: ...is unit when installed For attic or crawl space installation horizontal furnaces may be installed on combustible wood flooring or by using support brackets See Figure 1 6 IMPORTANT If installing in a...

Page 6: ...RIZONTAL MODELS TOP LEFT SIDE FRONT RIGHT SIDE BOTTOM 24 1 2 26 13 16 26 5 8 24 11 32 24 11 32 19 32 9 16 24 7 16 28 1 16 26 5 8 14 3 8 11 1 2 34 1 5 8 DIA 23 15 20 D 7 8 DIA 7 8 DIA 19 32 19 32 3 4 1...

Page 7: ...15 5 8 23 5 8 0 0 0 1 3 6 140 lbs 15 24 1 2 23 11 32 15 5 8 23 5 8 0 0 0 1 3 6 150 lbs TOP BOTTOM 24 1 2 19 3 4 C A B D LOW VOLTAGE GAS CONNECTION ELECTRIC CONNECTION E 26 5 8 26 13 16 6 3 16 20 3 8 2...

Page 8: ...uding evaporator coil if used of the entire system should not exceed 0 5 w c Be sure to have adequate space for unit filter IMPORTANT Some high efficiency filters have a greater than normal resistance...

Page 9: ...NTO THE LIVING SPACE AND CREATE POTENTIALLY HAZARDOUS CONDITIONS INCLUDING CARBON MONOXIDE POISONING OR DEATH 2 If summer air conditioning is desired position the indoor coil on the top of the unit In...

Page 10: ...unted in a closet the door must be closed when making this check of the installation DO NOT reset the overtemperature switch without taking corrective action to assure that an adequate supply of combu...

Page 11: ...ht construction contemporary construction outside air may still be required for the furnace to operate and vent properly Outside air openings should be sized the same as for a confined space FIGURE 7...

Page 12: ...uare inch for each 2000 BTUH of total input rating for all equipment in the enclosure see Figure 8 Here are typical duct sizes FIGURE 8 OUTSIDE AIR USING A HORIZONTAL INLET OUTLET B Method 2 One perma...

Page 13: ...SI Z223 1 AND OR THE NATURAL GAS INSTALLATION CODE CSA B149 1 2 FOR PROPER INSTALLATION PRACTICES SINGLE WALL VENT CONNECTORS TO B 1 VENT OR MASONRY CHIMNEYS MAY BE USED UNDER THE GUIDELINES OF THE NA...

Page 14: ...gher than any portion of a building within 10 feet 2 A type B 1 gas vent shall terminate at least 5 feet in vertical height above the highest connected equipment draft hood or flue collar 3 Must rise...

Page 15: ...operate a summer exhaust fan Close fireplace dampers 4 Follow the lighting instructions Place the appliance being inspected into operation Adjust the thermostat so the appliance will operate continuou...

Page 16: ...in size to prevent undue pressure drop and never smaller than the pipe size to the combination gas valve on the furnace Refer to Table 2 for the recom mended pipe size for natural gas and Table 3 for...

Page 17: ...ns The valve can be converted to use liquefied petroleum LP gas by replacing the pressure regulator spring with the conversion kit spring This LP kit spring allows the regulator to maintain the proper...

Page 18: ...the LP supplier adjust the line pressure at the regulator See Table 3 NOTE Depending on the amount of LP vapor and the outdoor ambient temperature the LP storage tank may require supplemental heat to...

Page 19: ...t off the manual main gas valve and remove the gas manifold 2 Replace the orifice spuds 3 Reassemble in reverse order 4 Turn the gas supply back on and check for proper operation and manifold pressure...

Page 20: ...available from the furnace manufacturer s Parts Department are acceptable Generally all thermostats that are not of the current robbing type are compatible with the integrated furnace control used NOT...

Page 21: ...with identical control boards 1 thermostat per 2 furnaces IMPORTANT Only bottom returns can be used No more than two furnaces can share the same supply and return Furnaces must have same heating and...

Page 22: ...22 I400 FIGURE 16 UT Electronic Controls 1028 928 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION a099201...

Page 23: ...23 FIGURE 17 UTEC 1028 928 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION a099301...

Page 24: ...lations are the best method Example 900 BTU ft3 Regional Natural Gas Heating Value I H Q 25000 900 27 78 ft 3 I Sea Level input per burner 25000 H Sea Level Heating Value 900 Q 27 78 ft 3 Natural Gas...

Page 25: ...23 000 22 000 21 000 20 000 19 000 18 000 17 000 16 000 All calculations are performed by using the first three columns of information only Before beginning any calculations determine the individual...

Page 26: ...site with manifold pressure adjustment to ensure that an actual 10 reduction in input rate is achieved Once this field adjustment has been made the label shown in Figure 18 rmust be affixed in a consp...

Page 27: ...don t light the system goes through another ignition sequence It does this up to four times 7 The main blower starts approximately 20 seconds after the burners ignite 8 When the thermostat W Heat Call...

Page 28: ...inducer run for 3 minutes before another ignition attempt is made NOTE The following applies only to units manufactured before third Quarter 2003 After a 30 second inter purge inducer runs continuous...

Page 29: ...to the furnace as possible FIGURE 21 TEMPERATURE RISE MEASUREMENT GAS FURNACE DIRECT DRIVE INSTRUCTIONS FOR CHANGING BLOWER SPEED DISCONNECT THE ELECTRICAL SUPPLY TO THE FURNACE BEFORE ATTEMPTING TO...

Page 30: ...30 BLOWER PERFORMANCE DATA 80LJ DOWNFLOW MODELS ONLY BLOWER PERFORMANCE DATA 80PJ UPFLOW HORIZONTAL MODELS...

Page 31: ...ck PRESSURE SWITCH This furnace is equipped with a normally open pressure switch that monitors pressure conditions within the furnace vent system during the heating cycle There are several reasons for...

Page 32: ...alified installer service agency or the gas supplier to prevent the possibility of overheating due to an accumulation of dust and dirt on the windings or on the motor exterior Air filters should be ke...

Page 33: ...or a filter base For systems with a return air filter grill or multiple filter grills can have a filter installed at each of the return air openings DO NOT DOUBLE FILTER THE RETURN AIR DUCT SYSTEM DO...

Page 34: ...D SIDE RETURN FIGURE 27 DOWNFLOW FILTER INSTALLATION FILTER ROD 45 24095 01 FILTER ROD SUPPORT ANGLE AE 60520 01 FILTER SUPPORT ANGLE SEE ANGLE DETAIL AE 61883 01 FILTER ROD SUPPORT ANGLE AE 60520 01...

Page 35: ...S OF THE VENT PIPE THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS PLACEMENT OF COMBUSTIBLE MATERIALS ON...

Page 36: ...F Did a limit open during ignition trial If yes go to D Check line voltage between HEAT and NEUTRAL on IFC Check wires connections and continuity between IFC and IBM Check IBM capacitor Check IBM CHE...

Page 37: ...37 FIGURE 29 FOR MODELS WITH UT ELECTRONIC CONTROLS 1028 928 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION...

Page 38: ...38 FIGURE 30 FOR MODELS WITH UT ELECTRONIC CONTROLS 1012 925 OR INVENSYS CLIMATE CONTROLS ICC H1MC7 01 INTEGRATED FURNACE CONTROL AND HOT SURFACE IGNITION...

Page 39: ...39...

Page 40: ...40 CM 0604 MANUFACTURED BY ICECO 5600 OLD GREENWOOD ROAD FORT SMITH ARKANSAS 72908...

Reviews: