ELEVATION SERIES CIM CUBER
HIGH PRESS CUT‐OUT AND FAN CYCLE SWITCH
51
High Pressure Cut-out
(left)
The High Pressure Cut‐out is set to open at
450 psig and de‐energizes the Contactor as a
safety on the unit.
Fan Cycle Control
(right)
The Fan Cycle Control helps maintain head
pressure in cooler ambient temps. The control
closes at 250 psig, energizing the Fan Motor
and opens at 200 psig.
Troubleshooting
High Pressure Cut-out
The High Pressure Cut‐out opens at 450 psig to de‐energize the Contactor and shutdown the
Compressor. The control re‐closes at 350 psig. Should the control open during the Freeze Cycle,
the unit may go into Error 1 state, indicating the Freeze Cycle has run for more than 1 hour. To
quickly check the unit operating pressure, run a Diagnostic Cycle with stub gauges on the unit.
A dirty or blocked Condenser, failed Fan Cycle Control, failed Fan Motor, high side restriction or
refrigerant over charge can be the cause.
Fan Cycling Control
The Fan Cycle Control closes on pressure rise at 250 psig and opens on pressure drop at 200 psig
to maintain head pressure in cooler ambient conditions. The cut‐in and cut‐out should never be
erratic. Should the contacts of the control close and/or open outside these parameters, the con‐
trol should be replaced.
Summary of Contents for CIM0320
Page 3: ...ELEVATION SERIES CIM CUBERS TABLE OF CONTENTS ...
Page 36: ...ELEVATION SERIES CIM CUBERS BUTTON FUNCTIONS 33 ...
Page 51: ...ELEVATION SERIES CIM CUBERS EVAPORATOR REPLACEMENT 48 ...
Page 67: ...ELEVATION SERIES WIRING DIAGRAM 64 CIM0530 0636 0836 1126 and 1136 REMOTE COOLED UNITS ...
Page 68: ...ELEVATION SERIES WIRING DIAGRAM 65 CIM0535 0835 and 1135 REMOTE COOLED UNITS ...