Recommended power line sizes
This appendix discusses how to determine the power line lengths running from
your N series system to the power source.
Recommended AC power line sizes
Longer AC power feeds need to be properly designed to preserve voltage levels to
the equipment. The wiring from the breaker panel to the power strip, which
supplies power to your N6200 series system and storage expansion units, can often
exceed 50 feet.
Note:
Total AC wire length = breaker to wall or ceiling extension cable or
ceiling drop.
The following table lists the recommended conductor size for 2% voltage drop for
a particular distance in feet (taken from the
Radio Engineer's Handbook
).
Table 14. 110V, single phase recommended conductor sizes
110V, single-phase
20A circuit
30A circuit
40A circuit
50A circuit
25 feet
12 AWG
10 AWG
8 AWG
8 AWG
50 feet
8 AWG
6 AWG
6 AWG
4 AWG
75 feet
6 AWG
4 AWG
4 AWG
2 AWG
Table 15. 220V, single phase recommended conductor sizes
220V, single-phase
20A circuit
30A circuit
40A circuit
50A circuit
25 feet
14 AWG
12 AWG
12 AWG
10 AWG
50 feet
12 AWG
10 AWG
8 AWG
8 AWG
75 feet
10 AWG
8 AWG
6 AWG
6 AWG
The following table list the approximate equivalent wire gauge (American Wire
Gauge (AWG) to Harmonized Cordage).
Table 16. American Wire Gage to Harmonized Cordage equivalents
AWG
8
10
12
Harmonized, mm-mm
1
4.0
2.5
1.5
1
mm-mm = millimeter squared
© Copyright IBM Corp. 2013
103
Summary of Contents for N6270
Page 12: ...xii IBM System Storage N6200 Series Hardware and Service Guide...
Page 16: ...xvi IBM System Storage N6200 Series Hardware and Service Guide...
Page 18: ...xviii IBM System Storage N6200 Series Hardware and Service Guide...
Page 20: ...xx IBM System Storage N6200 Series Hardware and Service Guide...
Page 46: ...20 IBM System Storage N6200 Series Hardware and Service Guide...
Page 130: ...104 IBM System Storage N6200 Series Hardware and Service Guide...
Page 134: ...108 IBM System Storage N6200 Series Hardware and Service Guide...
Page 146: ...120 IBM System Storage N6200 Series Hardware and Service Guide...
Page 147: ......
Page 148: ...Printed in USA GA32 0838 04...