120
Updated
28/02/01
To access IBM information specific to your country via the World Wide Web, use address: http://www.ibm.com/pc
Appendix C: UPS Runtime Estimate (minutes)
Servers
# Pwr. Cords Std/Max
Watts Load Max./Typ.
1
Netfinity 1000
2
1/1
225/160
Netfinity 3000
2
1/1
225/160
Netfinity 3500 M20
2
1/1
430/300
Netfinity 4000R
1/1
150/105
xSeries 200
2
1/1
350/245
xSeries 220
2
1/1
350/245
xSeries 230 / Netfinity 5100
2
1/3
450/315
xSeries 240 / Netfinity 5600
2
2/3
450/315
xSeries 330
2
1/1
200/140
xSeries 340 / Netfinity 4500R
2
1/2
390/270
Netfinity 6000R
2
1/4
525/395
Netfinity 7100
2
2/4
475/330
Netfinity 7600
2
3/4
475/330
Netfinity 8500R
2
3/3
1450/1015
Other Devices
Fibre Channel RAID Controller Unit (P/N SFCU1xx)
2
2/2
160/105
FAStT500 Storage Server (P/N 00N69xx)
2
2/2
200/140
FAStT EXP500 Storage Expansion Unit (P/N 00N71xx)
2
2/2
350/245
FAStT200 Storage Server (P/N 19K11xx)
2
2/2
390/275
FAStT200 HA Storage Server (P/N 19K11xx)
2
2/2
390/275
EXP200 Storage Expansion Unit
2
1/2
350/280
EXP300 Storage Expansion Unit
2
2/2
360/285
SAN Fibre Channel Switch 8-port (P/N 2109S08)
1/2
200/n/a
SAN Fibre Channel Switch 16-port (P/N 2109S16)
1/2
200/n/a
SAN Data Gateway Router (SE) (P/N 2108R3S)
1/1
90/n/a
DLT Tape Autoloader and Library (P/N 00N79xx)
1/1
135/n/a
NetMEDIA Storage Expansion Unit EL (P/N 03K8756)
2/2
185/130
1. This table represents general guidelines for selecting the appropriate UPS based on minimum and typical runtime estimates. A ‘maximum configuration’ load will result in ‘minimum’
UPS runtime. ‘Typical’ loads are based on a production system running at approximately 70% of maximum capacity. The ‘typical’ loads represent a more likely configuration and,
therefore, a more likely estimate of runtime. Customer environments are unique and are unlikely to be precisely represented by any of the specific entries in the table.
2. Power-Factor Corrected (PFC) power supply.
Tower
Rack Mounted
EMEA
P/N
SU-700iNET
P/N
SUP072Y
SU-1000iNET
P/N
SUP102Y
SU-1400iNET
P/N
SUP142Y
SU-2200iNET
P/N
06P60xx
6
SU-
1400RMiB
P/N 14RIxxx
7
SU-
3000RMiB
P/N 30RIxxx
7
SU-
5000RMiB
P/N 37L6862
US
P/N
SU-
700NET
94G3134
SU-
1000NET
94G3135
SU-
1400NET
94G3136
Not Available
SU-
1400RMB
94G6674
SU-
3000RMB
94G6676
SU-
5000RMB
37L6861
UPS Attributes
1
Communications Links to Servers
1
1
1
1
1
3
3
Color
black
black
black
beige
black
black
black
EIA Height
-
-
-
-
3U
3U
5U
EMEA Models
50 or 60 Hz, single phase, VAC:
220-240 (208)
2
220-240 (208)
2
220-240 (208)
2
220-240 (208)
2
220-240 (208)
2
220-240 (208)
2
220-240 (xxx)
2,
3
10 Amp, IEC 320-C13
(Device) receptacles
4
4
4
8
4
8
8
16 Amp, IEC 320-C19
(PDU P/N 2PDUxxx) receptacles
-
-
-
1
-
1
2
Line Cord Receptacle (IEC 320- )
C14
C14
C20
C20
C14
C20
TB
5
US Models
50 or 60 Hz, single phase, VAC:
120 (120)
2
120 (120)
2
120 (120)
2
-
120 (120)
2
120 (120)
2
200-220 (208)
2
Receptacles (NEMA 5-15R)
4
6
6
-
6
8
-
10 Amp, IEC 320-C13
(Device) receptacles
-
-
-
-
-
-
8
16 Amp, IEC 320-C19
(PDU 94G7450) receptacles
-
-
-
-
-
-
2
4
Line Cord Length, NEMA Plug
6 ft., 5-15P
6 ft., 5-15P
6 ft., 5-15P
-
6 ft., L5-15P
6 ft., L5-30P
8 ft., L5-30P
Summary of Contents for eServer xSeries
Page 20: ...19 Updated 28 02 01...
Page 28: ...27 Updated 28 02 01...
Page 36: ...35 Updated 28 02 01...
Page 44: ...43 Updated 28 02 01...
Page 58: ...57 Updated 28 02 01...
Page 66: ...65 Updated 28 02 01...
Page 92: ...91 Updated 28 02 01...
Page 96: ...95 Updated 28 02 01...
Page 116: ...115 Updated 28 02 01...
Page 120: ...119 Updated 28 02 01...