Each power supply provides up to 950 watts. Therefore, the total power available
for the BladeCenter S system would be as follows:
v
Non-redundant power policy: 1900 watts
v
Power module redundancy power policy: 950 watts
v
AC power source redundancy power policy: 950 watts
Four power supplies attached to 110 V ac power sources
In this example, there are four power supplies that are attached to two separate
power sources. The power sources could each be different dedicated branch
circuits from your circuit breaker panel:
v
Power source A could be your utility provider
v
Power source B could be your UPS service
Power
module 3
Power
module 4
Power
module 1
Power
module 2
!
!
!
!
Power
source A
Power
source A
Power
source B
Power
source B
Each power supply provides up to 950 watts. Therefore, the total power available
for the BladeCenter S system would be as follows:
v
Non-redundant power policy: 3477 watts
v
Power module redundancy power policy: 2850 watts
Chapter 2. Planning for the physical environment
33
Summary of Contents for 88861TU
Page 1: ...IBM BladeCenter S Type 7779 8886 Planning Guide...
Page 2: ......
Page 3: ...IBM BladeCenter S Type 7779 8886 Planning Guide...
Page 30: ...24 BladeCenter S Type 7779 8886 Planning Guide...
Page 44: ...38 BladeCenter S Type 7779 8886 Planning Guide...
Page 76: ...70 BladeCenter S Type 7779 8886 Planning Guide...
Page 118: ...112 BladeCenter S Type 7779 8886 Planning Guide...
Page 124: ...118 BladeCenter S Type 7779 8886 Planning Guide...
Page 128: ...122 BladeCenter S Type 7779 8886 Planning Guide...
Page 129: ......
Page 130: ...Part Number 60Y1614 Printed in USA 1P P N 60Y1614...