IBM and non-IBM racks
Verify that you are not exceeding the maximum weight load limits for IBM and
non-IBM racks.
Table 2 shows the maximum weight limits for IBM NetBAY racks and expansion
units that are recommended for use with BladeCenter S chassis. The table shows
the maximum number of BladeCenter S chassis that can be installed in a NetBAY
rack when the rack is:
v
Installed in place and sitting on the rack leveling pads.
v
Being relocated and is sitting on the rack castors.
For on-site relocation of the rack on castors, the maximum number of BladeCenter
S chassis, including the power distribution units (PDUs) to support the
configuration, is based on a 14-degree stability requirement established under IBM
safety guidelines.
Table 2. Rack weight load limits
Rack
Rack weight
Maximum
allowable rack
weight load
Maximum
number of fully
loaded
BladeCenter S
units with rack
on leveling pads
or bolted to the
floor
On-site
relocation, rack
on casters,
maximum
number of
BladeCenter S
units
Office
Enablement Kit
40.8 kg (90 lb)
223 kg (491 lb)
1
1
NetBAY 11
37 kg (75 lb)
216 kg (475 lb)
1
1
NetBAY 42
Enterprise Rack
261 kg (575 lb)
928 kg (2045 lb)
6
3
NetBAY 42
Enterprise
Expansion
Cabinet
234 kg (511 lb)
928 kg (2045 lb)
6
3
NetBAY 42
Standard Rack
119 kg (262 lb)
765 kg (1683 lb)
6
3
NetBAY 42
Standard
Expansion
Cabinet
112 kg (246 lb)
739 kg (1626 lb)
6
3
NetBAY 25
Standard Rack
95 kg (209 lb)
466 kg (1025 lb)
3
3
NetBay S2 25
Standard Rack
100 kg (221 lb)
667 kg (1471 lb)
3
3
NetBay S2 42
Standard Rack
125 kg (275 lb)
1032 kg (2275 lb)
6
6
When determining your floor load limits, use the combined weight of the rack,
populated BladeCenter S chassis, PDUs, and other rack mounting hardware to
ensure the installation site can safely support the total weight. Consult your local
building engineer to understand the weight limits for your site. Use the “Rack
installation worksheet” on page 87 to record your information.
Chapter 2. Planning for the physical environment
27
Summary of Contents for 88861TU
Page 1: ...IBM BladeCenter S Type 7779 8886 Planning Guide...
Page 2: ......
Page 3: ...IBM BladeCenter S Type 7779 8886 Planning Guide...
Page 30: ...24 BladeCenter S Type 7779 8886 Planning Guide...
Page 44: ...38 BladeCenter S Type 7779 8886 Planning Guide...
Page 76: ...70 BladeCenter S Type 7779 8886 Planning Guide...
Page 118: ...112 BladeCenter S Type 7779 8886 Planning Guide...
Page 124: ...118 BladeCenter S Type 7779 8886 Planning Guide...
Page 128: ...122 BladeCenter S Type 7779 8886 Planning Guide...
Page 129: ......
Page 130: ...Part Number 60Y1614 Printed in USA 1P P N 60Y1614...