6. COMMISSIONING AND ADDITIONAL INSTRUCTIONS
76
After the installation:
• Make sure that the motor is installed correctly.
• Make sure that the motor terminals are not connected to mains.
• Make sure that the AC drive and the motor are grounded.
• Make sure that you select the mains cable, the brake cable, and the motor cable correctly (see chapter 4.3 Cable dimen
sioning and selection).
• Make sure that the control cables are as far as possible from the power cables. See chapter 4.6 Cable installation.
• Make sure that the shields of the shielded cables are connected to an earth terminal that is identified with .
• Do a check of the tightening torques of all the terminals.
• Make sure that no power correction capacitors are connected to the motor cable.
• Make sure that the cables do not touch the electrical components of the drive.
• Make sure that the common inputs of the digital input groups are connected to +24 V or ground of the I/O terminal or the
external power source.
• Do a check of the quality and quantity of the cooling air. See chapter 3.4 Cooling and Table 14 The necessary quantity of
cooling air.
• Make sure that there is no condensation on the inner surfaces of the AC drive.
• Make sure that there are no unwanted objects in the installation space.
• Before you connect the drive to mains, do a check of the installation and the condition of all the fuses and other protective
devices.
6.3 OPERATION OF THE MOTOR
6.3.1 CHECKS BEFORE STARTING THE MOTOR
Before you start the motor, do these checks.
• Make sure that all the START and STOP switches that are connected to the I/O terminals are in the STOP position.
• Make sure that you can start the motor safely.
• Activate the Start-up wizard. See the Application Manual for the AC drive that you have.
• Set the maximum frequency reference (that is, the maximum speed of the motor), so that it agrees with the motor and the
device that is connected to the motor.
6.4MEASURINGTHECABLEANDMOTORINSULATION
Theinsulationchecksofthemotorcable
1) Disconnect the motor cable from the terminals U, V, and W and from the motor.
2) Measure the insulation resistance of the motor cable between phase conductors 1 and 2, between phase conductors 1
and 3, and between phase conductors 2 and 3.
3) Measure the insulation resistance between each phase conductor and the earth conductor.
4) The insulation resistance must be
>
1 MΩ at the ambient temperature of 20 °C (68 °F).
N800A
Summary of Contents for N800 Series
Page 2: ...ISSUEDATE 2015 06 26 VER 1 ...
Page 3: ......
Page 19: ...3 MOUNTING 3 2 2 WALL MOUNTING OF MR5 Fig 3 ThedimensionsoftheACdrive MR5 13 N800A ...
Page 20: ...3 MOUNTING 3 2 3 WALL MOUNTING OF MR6 Fig 4 ThedimensionsoftheACdrive MR6 14 N800A ...
Page 21: ...3 MOUNTING 3 2 4 WALL MOUNTING OF MR7 Fig 5 ThedimensionsoftheACdrive MR7 15 N800A ...
Page 23: ...3 MOUNTING 3 2 6 WALL MOUNTING OF MR8 IP00 Fig 7 ThedimensionsoftheACdrive MR8 IP00 17 N800A ...
Page 52: ...4 POWERCABLING 46 3 Removethecablecover MR8 MR9 N800A ...
Page 53: ...4 POWERCABLING 47 4 Removethecableentryplate MR8 MR9 N800A ...
Page 54: ...4 POWERCABLING 48 5 MR9only Loosenthescrewsandremovethesealingplate N800A ...
Page 55: ...4 POWERCABLING 49 6 RemovetheEMCshieldplate A ThewingnutinMR8 A MR9 N800A ...
Page 80: ...5 CONTROLUNIT 74 Fig 30 Thegalvanicisolationbarriers A Thecontrolunit B Thepowerunit N800A ...
Page 101: ......