4. POWER CABLING
1. A power cable for a fixed installation. A cable for the specified mains voltage. A shielded cable is not necessary. We recom-
mend an MCMK cable.
2. A symmetrical power cable with a concentric protection wire. A cable for the specified mains voltage. We recommend an
MCMK cable. See Fig. 22.
3. A symmetrical power cable with a compact low-impedance shield. A cable for the specified mains voltage. We recommend
an MCCMK, or an EMCMK cable. We recommend that the cable transfer impedance (1...30MHz) is a maximum of 100 mΩ/m.
See Fig. 22.
* For the EMC level C2, it is necessary to have a 360º earthing of the shield with cable glands in the motor end.
4. A screened cable with a compact low-impedance shield, for example a JAMAK, or an SAB/ÖZCuY-O cable.
Fig. 22: Cables with PE conductors
A. The PE conductor and the shield C. The shield
B. The PE conductors
In all the frames, to obey the EMC requirements, use the default values of the switching frequencies.
If you installed a safety switch, make sure that the EMC protection continues from the start of the cables until their ends.
4.2 UL STANDARDS ON CABLING
To obey the UL (Underwriters Laboratories) regulations, use a UL-approved Class 1 copper wire with a minimum heat resistance
of 60 or 75 °C (140 or 167 °F).
You can use the drive on a circuit that gives a maximum of 100 000 rms symmetrical amperes, and a maximum of 600 V, when
the drive is protected by Class T and J fuses.
4.3 CABLE DIMENSIONING AND SELECTION
These instructions are valid only for processes that have 1 motor and 1 cable connection from the AC drive to the motor. In
other conditions, speak to the manufacturer to get more information.
33
∙∙
N800A
Summary of Contents for N800 Series
Page 2: ...ISSUEDATE 2015 06 26 VER 1 ...
Page 3: ......
Page 19: ...3 MOUNTING 3 2 2 WALL MOUNTING OF MR5 Fig 3 ThedimensionsoftheACdrive MR5 13 N800A ...
Page 20: ...3 MOUNTING 3 2 3 WALL MOUNTING OF MR6 Fig 4 ThedimensionsoftheACdrive MR6 14 N800A ...
Page 21: ...3 MOUNTING 3 2 4 WALL MOUNTING OF MR7 Fig 5 ThedimensionsoftheACdrive MR7 15 N800A ...
Page 23: ...3 MOUNTING 3 2 6 WALL MOUNTING OF MR8 IP00 Fig 7 ThedimensionsoftheACdrive MR8 IP00 17 N800A ...
Page 52: ...4 POWERCABLING 46 3 Removethecablecover MR8 MR9 N800A ...
Page 53: ...4 POWERCABLING 47 4 Removethecableentryplate MR8 MR9 N800A ...
Page 54: ...4 POWERCABLING 48 5 MR9only Loosenthescrewsandremovethesealingplate N800A ...
Page 55: ...4 POWERCABLING 49 6 RemovetheEMCshieldplate A ThewingnutinMR8 A MR9 N800A ...
Page 80: ...5 CONTROLUNIT 74 Fig 30 Thegalvanicisolationbarriers A Thecontrolunit B Thepowerunit N800A ...
Page 101: ......