3. MOUNTING
Table 13: The minimum clearances around the AC drive
* For a drive with IP54 / UL Type 12, the minimum clearances A and B are 0 mm / 0 in.
Table 14: The necessary quantity of cooling air
30
Frame
Minimum clearance[mm]
Minimum clearance[in]
MR4
MR5
MR6
MR7
MR8
MR9
A*
20
20
20
20
20
20
B*
20
20
20
20
20
20
C
100
120
160
250
300
350
D
50
60
80
100
150
200
A*
0.8
0.8
0.8
0.8
0.8
0.8
B*
0.8
0.8
0.8
0.8
0.8
0.8
C
3.9
4.7
6.3
9.8
11.8
13.8
D
2.0
2.4
3.1
3.9
5.9
7.9
The quantity of cooling
air [
㎥
/h]
45
75
190
185
335
621
Frame
MR4
MR5
MR6
MR7
MR8
MR9
The quantity of cooling
air [CFM]
26.5
44.1
111.8
108.9
197.2
365.2
N800A
Summary of Contents for N800 Series
Page 2: ...ISSUEDATE 2015 06 26 VER 1 ...
Page 3: ......
Page 19: ...3 MOUNTING 3 2 2 WALL MOUNTING OF MR5 Fig 3 ThedimensionsoftheACdrive MR5 13 N800A ...
Page 20: ...3 MOUNTING 3 2 3 WALL MOUNTING OF MR6 Fig 4 ThedimensionsoftheACdrive MR6 14 N800A ...
Page 21: ...3 MOUNTING 3 2 4 WALL MOUNTING OF MR7 Fig 5 ThedimensionsoftheACdrive MR7 15 N800A ...
Page 23: ...3 MOUNTING 3 2 6 WALL MOUNTING OF MR8 IP00 Fig 7 ThedimensionsoftheACdrive MR8 IP00 17 N800A ...
Page 52: ...4 POWERCABLING 46 3 Removethecablecover MR8 MR9 N800A ...
Page 53: ...4 POWERCABLING 47 4 Removethecableentryplate MR8 MR9 N800A ...
Page 54: ...4 POWERCABLING 48 5 MR9only Loosenthescrewsandremovethesealingplate N800A ...
Page 55: ...4 POWERCABLING 49 6 RemovetheEMCshieldplate A ThewingnutinMR8 A MR9 N800A ...
Page 80: ...5 CONTROLUNIT 74 Fig 30 Thegalvanicisolationbarriers A Thecontrolunit B Thepowerunit N800A ...
Page 101: ......