INVERTER POOL HEAT PUMP 

 

USER MANUAL 

 

 

 

 

 

 

 
 

Summary of Contents for MSC130

Page 1: ...INFINITY INVERTER POOL HEAT PUMP USER MANUAL ...

Page 2: ...nsion 7 D Installation guidance 8 1 Installation reminder 8 2 Wiring 11 3 Electric wiring diagram 12 4 References for protecting devices and cable specification 12 E Operation guidance 13 1 Touchpad Functions 13 2 Operation Instructions 13 F Testing 15 1 Inspect heat pump before use 15 2 Leakage detection notice and method 15 3 Trial 16 G Maintenance 17 H Trouble shooting for common faults 18 I Wa...

Page 3: ...done online here https eziheat com au warranty registration We pride ourselves on quality and service so if you have any technical questions or require any further information please contact our friendly team at support eziheat com au We hope you ll enjoy using our energy saving heat pumps Thank you The EZIHEAT Team HEAT PUMP INFORMATION RECORD Heat Pump Model _____________________________________...

Page 4: ... like which if not correctly performed or adhered to could result in personal injury or injury to a third party These signs are rare but are extremely important 1 Keep the heat pump away from fire sources b The heat pump must be placed in a well ventilated area outdoors Indoor or enclosed areas are not allowed and will void your warranty c Repair and disposal must be carried out by a trained autho...

Page 5: ...ing effect please install heat preservation insulation on pipes between swimming pool and heat pump and please use a recommended pool cover on the swimming pool i Connecting pipes from the swimming pool to the heat pump should be less than 10m j If a repair is required please contact the EZIHEAT team support eziheat com au All repair practiced by non professional licenced persons is prohibited 3 S...

Page 6: ... your heat pump 1 Transportation a Always keep upright b Do not lift heat pump via the water unions Otherwise the titanium heat exchanger may be damaged 2 Accessories Connection of the condensate drainage kit ...

Page 7: ...nd low pressure protection h Full protection on electrical system 4 Operating range To provide you comfort and pleasure please set swimming pool water temperature efficiently and economically The heat pump air temperature operation range is 10 C 43 C and its ideal operation for best performance is operation range between air 15 C 25 C 5 Introduction of different modes a The heat pump has two modes...

Page 8: ...y will not be guaranteed out of this range Please take into consideration that the pool heat pump performance and parameters are different under various conditions Related parameters are subject to adjustment periodically for technical improvement without further notice For details please refer to nameplate ...

Page 9: ...fication without notice Note The picture above is the specification diagram of the pool heat pump for technician s installation and layout reference only The product is subject to adjustment periodically for improvement without further notice ...

Page 10: ...stallations must be installed in line with the relevant building codes and standards of their current state or local governing body for all electrical mechanical and water services to prevent danger or damage to the heat pump a Location and clearances The inverter pool heat pump should be installed with the required ventilation space ...

Page 11: ...ater pipe connection The inlet and outlet water unions must be plumbed in rigid pvc pipes Flexible hoses must not be used DO NOT install water pipes in a way that they pass behind the heat pumps evaporator ...

Page 12: ...nded pump must adhere to the specification flux of the heat pump refer to the technical parameters 4 When the heat pump is running there will be condensation water discharged from the bottom please pay attention to it Install the drainage nozzle accessory into the hole and clip it well then connect a pipe drain hose to drain the condensation water away for the heat pump 2 Wiring a Connect the heat...

Page 13: ...lug is not allowed 2 The swimming pool heat pump must be earthed well 4 References for protecting devices and cable specification MODEL MSC90 MSC130 MSC170 MSC210 MSC280 MSC350s Rated Current 10 5 14 5 18 21 24 12 A Breaker Rated Residual Action Current 30 30 30 30 30 30 mA 1 Above data is subject to modification without notice Note The data above is associated to power cables less than 10m If pow...

Page 14: ...Off 2 Wi Fi setting 1 Lock Unlock Screen 2 Heating mode 18 40 C 3 Cooling mode 12 30 C 4 Auto mode 12 40 C 1 Boost 2 Silence Temperature Setting Attention a The controller has power down memory function and will not display when locked b The buttons will turn dark when touchpad is locked ...

Page 15: ...etting point automatic cooling mode starts When water inlet temperature is lower than setting point automatic heating mode starts 2 Silence Boost mode selection Press to switch among boost mode silent mode Default mode boost Please choose boost mode for initial heating e Wi Fi DOWNLOAD InverGo App from App stores then follow instruction When the screen is on unlocked press and hold for 3 seconds a...

Page 16: ...he interval between manual defrosting should be more than 30 minutes g Round Controller Running Status Checking 1 Press for 5 seconds it will enter running status mode 2 During this time the display will show the status symbol C0 and its corresponding value 3 Change status through and the corresponding value also changes 4 Press to quit Running Status Checking mode 5 Running status checking table ...

Page 17: ... Water pump running way 0 Continuation 1 Water temp control 2 time water temp control 1 2 P1 Time setting only available when the water pump running way is set to 2 10 120 min 5 min 60 min P2 Compressor continuously running time in defrosting mode 30 90min 1min 35 min P3 Defrosting start temp 17 0 1 7 P4 Defrosting running time 1 12min 1min 12 min P5 Defrosting quit temp 8 30 1 13 P6 Single pump o...

Page 18: ... chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe d Vacuum the heat pump completely before welding Welding should only be carried out by professional personnel in service center e Please stop immediately if a gas leak occurs and contact your local service center 3 Trial Run a The circulation pump must start before the heat pump and stop after the...

Page 19: ... up to a seven degree differential If the temperature differential goes above 7 degrees the built in flow switch or E6 error will be displayed indicating insufficient water flow has been detected Recommended procedure to set temperature differential 1 Open all 2 way 3 way valves on the by pass assembly on the inlet outlet pipes 2 Fully close the by pass and switch the heat pump on to the required ...

Page 20: ...t pipe to let the water flow out When the water in heat pump freezes in winter season the titanium heat exchanger may be damaged 2 Clean the heat pump with household detergents or clean water NEVER use gasoline thinners or any similar fuel 3 Check bolts cables and connections regularly 4 If repairs or removal is required please contact an authorized service center 5 Do not attempt to work on the e...

Page 21: ...operation d Vacuum system completely before welding Welding should only be carried out by professional person in a service center 2 Failure solution and code Failure Reason Solution No power Wait until the power recovers Heat pump doesn t run Power switch is off Switch on the power Fuse burned Check and change the fuse The breaker is off Check and turn on the breaker Fan running but with Evaporato...

Page 22: ...pes and filtration pump is running Check the bypass is opened and unit is commissioned Check the Water flow switch E7 Water outlet temp too high or too low protection Water flowrate in pipes Check if there is any blockage in the inlets outlets and through the pipes E8 High exhaust temp protection Compressor overheating Check if refrigerant gas is leaking check the connection of the sensor might ne...

Page 23: ... need to be changed P3 Gas exhaust temp sensor failure The sensor is running a short circuit damaged or not fixed properly Check the gas exhaust temperature sensor might need a replacement P4 Evaporator coil pipe temp sensor failure The sensor is running a short circuit damaged or not fixed properly Check the evaporative coil pipe Temperature sensor might need a replacement P5 Gas return temp sens...

Page 24: ...trol connection Water pump 230V voltage 500W capacity Breaker fuse Power Cable Not Supplied Earthing Power Supply 230V 50Hz Breaker fuse Not Supplied Power Supply 230V 50Hz Earthing External auxiliary input Water Pump ...

Page 25: ... pump 230V voltage 500W capacity Breaker fuse Not Supplied Earthing Power Supply 230V 50Hz Breaker fuse Not Supplied Power Supply 230V 50Hz Power Cable External auxiliary input Water Pump Contactor Earthing ...

Page 26: ...Water pump 400V voltage Breaker fuse Power Supply Not Supplied Power Cable 230V 50Hz Earthing Breaker fuse Not Supplied Power Supply 400V 50Hz Earthing External auxiliary input Water Pump Contactor ...

Page 27: ...ion 1 Water pump timer 2 Water pump wiring of Heat Pump Note The installer should connect 1 parallel with 2 as above picture To start the water pump condition 1 or 2 is connected To stop the water pump both 1 and 2 should be disconnected ...

Page 28: ...w the instructions below to connect a smart phone to the heat pump via a Wi Fi network It is crucial that the Wi Fi network signal strength is of high power at the heat pump location otherwise connection will not be achieved ...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ...EZIHEAT AUSTRALIA PTY LTD ABN 11 158 163 298 Phone 1300 363 555 Web eziheat com au Email info eziheat com au ...