Installation and Maintenance Manual
34
Detector Loop Installation Guide, continued
8. Follow this guide for the correct number of wire turns according to the perimeter size of the loop:
10 to 13 lf. = 5 turns 14 to 26 lf. = 4 turns 27 to 45 lf. = 3 turns 46 to 100 lf. = 2 turns
9. This guide is written from a design perspective, but installation workmanship practices are equally
important to insure proper operation and long loop life. The best way to insure a quality installation is
to employ a professional installer experienced with detector loops. A few important practices are:
A.
The slot in the surface should be cut ¼” wide x 1 ½” deep.
B.
The corners of the cut must be at an
angle or core drilled to relieve stress on the wires.
C.
After the wire is installed, the slot must be
completely backfilled with a non-hardening sealer. Note that if the loop wires are able to move in the
slot after the sealer has set, the detector may give false calls.
Detector Logic
HySecurity Gate Operators recommends that vehicle detectors be used for free open and obstruction
sensing logic only. The exception is in parking applications with our HTG 320 barrier arm operator where
a reset detector may be also used to close the gate. In applications employing our swing, vertical lift, or
sliding gate operators, closing logic cannot be used.
Loop Diagnostics
The following tests cannot guarantee a functioning loop, but failure of either test means that the loop is
definitely suspect, even though it may still be functioning at the time.
Test #1:
Resistance of the loop and lead-in wire should not exceed 4.0 Ohms.
Test #2:
The resistance to earth, as measured with a 500V “Megger”, should be 100 Megohms or more. Loops
may function at 10 Megohms or less but will not be reliable (e.g. when the ground is wet from rainfall).
Low resistance indicates broken or moisture saturated insulation. This is common if inappropriate wire
insulation has been used.
See also Detector and Loop Fault Diagnostics on page 39 for additional tests that may be performed with
HySecurity HY-5A detector modules.
Summary of Contents for HTG 320-2
Page 18: ...Installation and Maintenance Manual 10 Components of the Barrier Arm Gate Operator ...
Page 21: ...Installation and Maintenance Manual 13 46 ...
Page 22: ...Installation and Maintenance Manual 14 46 ...
Page 23: ...Installation and Maintenance Manual 15 ...
Page 43: ...Installation and Maintenance Manual 35 E95 ...
Page 48: ...Installation and Maintenance Manual 40 24 hr 7 day Timer Connection to Smart Touch Controller ...
Page 57: ...Installation and Maintenance Manual 49 24V 110A H BATTERY POWER SUPPLY FOR DC OPERATORS ...
Page 59: ...Installation and Maintenance Manual 51 ...
Page 60: ...Installation and Maintenance Manual 52 Parts Breakout ...
Page 61: ...Installation and Maintenance Manual 53 Parts Breakout ...
Page 62: ...Installation and Maintenance Manual 54 Parts Breakout AC Pumps MX000234 HVABY 000 CRT ...
Page 63: ...Installation and Maintenance Manual 55 Parts Breakout DC Pumps MX000234 HVABY 000 CRT ...
Page 64: ...Installation and Maintenance Manual 56 Parts Breakout ...
Page 67: ...Installation and Maintenance Manual 59 Smart Touch Controller Connections ...
Page 68: ...Installation and Maintenance Manual 60 Quick StrongArm Brake Valve adjustment Procedure ...