Description of Functions Available in the Installer Menu
Installer 1
[uC 0]
Set UL Usage Class:
This menu item is used to set the UL usage class, which must be
set by the installer before the operator will function. See page 17, step 2.
Installer 1a
[bu 0]
Select Buzzer Type:
This menu item selects the type of audible buzzer installed on the
machine. To set, push SELECT on the keypad, the display will flash 0, push OPEN and note the buzzer
volume. Push OPEN again and note the buzzer volume. If this tone is louder, push SELECT, if the first tone
was louder, push CLOSE for the louder tone, then push SELECT to lock in the louder tone.
Installer 2
[Fd 0]
Load Factory Defaults:
This menu item is used to globally restore all menu settings
back to new machine status. To activate, change the setting 0 to 1 and push the Menu button. The UL usage
class and the hand configuration will need to be set again.
Installer 3
[dg 0]
Set Solo, Master or Slave type:
This menu item is used to configure an operator as a
Master or a Slave operator in Master/Slave paired gate installations.
Installer 4
[Ch 0]
Set AC Charger or Solar:
This menu item only appears on 24 VDC battery machines
only and is set to solar only when there is no AC battery charger.
Installer 5
[Fo 0]
Enable Fire Dept. Open:
This menu item is used to enable the Fire Dept. Open input.
When set to [Fo_1] this input will override vehicle detectors, photo eyes and gate edges to open a gate. A
reset input is required before the gate can be closed.
Installer 6
[oC 0]
Enable Emergency Close:
This menu item is used to enable the Emergency Close
input. When set to [oC_1] this input will, with a constant hold input, override vehicle detectors, photo eyes
and gate edges to close a gate. A reset input is required before the gate can be opened.
Installer 7
[SE 6]
Inherent Sensor sensitivity:
. This menu item is to adjust the sensitivity of the internal
inherent sensor. Available settings are 1-9, with 9 being the least sensitive.
Installer 8
[SS 0]
Inherent Sensor function:
This menu item is only available in UL class 4 operators and
allows an option whereby the inherent sensor will only stop the gate.
Installer 9
[LC 0]
Leaf delay Close:
This menu item only appears if the operator is set up as a Master or a
Slave. Available settings are 1-7. Each increment adds ½ second, to a maximum of 3 ½ seconds time delay,
before the operator activates when commanded to close.
Installer 10
[Lo 0]
Leaf delay Open:
This menu item only appears if the operator is set up as a Master or a
Slave. Available settings are 1-7. Each increment adds ½ second, to a maximum of 3 ½ seconds time delay,
before the operator activates when commanded to open.
Installer 11
[rt 0]
Maximum run timer:
The maximum run timer has a default setting of 60 seconds. This
menu item allows an optional setting of 300 seconds, if changed to [rt_1].
Installer 12
[EC 0]
PEC (photo eye close) reverse to open:
The default for this menu item is for non-
reversal if the close photo eye is triggered. The optional setting of [EC_1] will cause the gate to reverse to
open for two seconds if triggered while closing.
Installer 13
[PC 0]
Set PEC – NO/NC:
The default for this menu item is for photo eyes with Normally Open
outputs. The optional setting of [PC_1] will require a Normally Closed output. If set for N.C. the connection is
also supervised and any open or short circuit fault will generate a FAL2 alert, which requires a Stop button
reset to re-enable any function if triggered.
Installer 14
[gC 0]
Set Edge input – NO/NC:
The default for this menu item is for edge sensor with
Normally Open outputs. The optional setting of [gC_1] will require a N.C. output.
Summary of Contents for HTG 320-2
Page 18: ...Installation and Maintenance Manual 10 Components of the Barrier Arm Gate Operator ...
Page 21: ...Installation and Maintenance Manual 13 46 ...
Page 22: ...Installation and Maintenance Manual 14 46 ...
Page 23: ...Installation and Maintenance Manual 15 ...
Page 43: ...Installation and Maintenance Manual 35 E95 ...
Page 48: ...Installation and Maintenance Manual 40 24 hr 7 day Timer Connection to Smart Touch Controller ...
Page 57: ...Installation and Maintenance Manual 49 24V 110A H BATTERY POWER SUPPLY FOR DC OPERATORS ...
Page 59: ...Installation and Maintenance Manual 51 ...
Page 60: ...Installation and Maintenance Manual 52 Parts Breakout ...
Page 61: ...Installation and Maintenance Manual 53 Parts Breakout ...
Page 62: ...Installation and Maintenance Manual 54 Parts Breakout AC Pumps MX000234 HVABY 000 CRT ...
Page 63: ...Installation and Maintenance Manual 55 Parts Breakout DC Pumps MX000234 HVABY 000 CRT ...
Page 64: ...Installation and Maintenance Manual 56 Parts Breakout ...
Page 67: ...Installation and Maintenance Manual 59 Smart Touch Controller Connections ...
Page 68: ...Installation and Maintenance Manual 60 Quick StrongArm Brake Valve adjustment Procedure ...