Troubleshooting
‐
Inline
Heater
Temperature
Limit
Switch
48
9.2
Inline
Heater
Temperature
Limit
Switch
The
chiller
is
equipped
with
a
mechanical,
temperature
limit
switch
that
disengages
(trips)
the
heater
in
the
event
of
a
malfunction
to
prevent
excessive
fluid
temperatures
that
could
result
in
fire
hazards.
If
the
switch
has
tripped
it
can
be
reset
by
performing
the
following
steps:
1.
Access
the
chiller’s
air
intake/filter
side
(refer
to
section
6.4
Internal
Access).
2.
Locate
the
temperature
limit
switch
(refer
to
3.
Figure
41).
4.
Unscrew
the
cap
on
the
temperature
limit
switch
to
access
the
green
reset
button.
5.
Press
the
reset
button
with
a
screwdriver
of
appropriate
size
until
a
tactile
click
is
felt.
If
the
button
is
loose
and
there
is
no
click
then
the
switch
is
already
closed.
If
the
button
will
not
remain
closed
(engaged)
after
attempting
to
press,
then
the
temperature
of
the
pipe,
in
which
the
inline
heater
is
located,
is
still
too
hot.
Allow
the
pipe
surface
to
cool
before
attempting
to
reset
the
switch.
6.
Reinstall
the
cap
on
the
temperature
limit
switch.
7.
Reinstall
the
air
intake
filter(s)
before
restarting
chiller.
9.3
Refrigeration
High
Pressure
Switch
WARNING
The
refrigeration
discharge
lines
may
be
extremely
hot
–
avoid
contact.
Resetting
of
the
refrigeration
high
pressure
switch
should
only
be
performed
by
qualified
personnel
equipped
with
proper
safety
gear
and
tools.
The
chiller’s
refrigeration
circuit
is
equipped
with
a
mechanical,
high
pressure
switch
that
disengages
(trips)
the
refrigeration
circuit
when
dangerously
high
pressures
occur
to
prevent
damage
to
the
refrigeration
system.
If
the
switch
has
tripped
it
can
be
reset
by
performing
the
following
steps:
1.
Access
the
chiller’s
air
intake/filter
side
(refer
to
section
6.4
Internal
Access).
2.
Locate
the
refrigeration
high
pressure
switch
(refer
to
3.
Figure
41).
4.
Depress
the
red
reset
button
until
a
tactile
click
is
felt.
5.
Reinstall
the
air
intake
filter(s)
before
restarting
chiller.
Hypertherm, Inc. Part Number: 810540
Summary of Contents for Koolant Koolers N-Series
Page 61: ...Appendix B Electrical Schematics PLC 59 PLC Hypertherm Inc Part Number 810540...
Page 62: ...Appendix B Electrical Schematics I O Module 60 I O Module Hypertherm Inc Part Number 810540...
Page 63: ...Appendix B Electrical Schematics Logic 61 Logic Hypertherm Inc Part Number 810540...
Page 73: ...Appendix E Declaration of Conformity 71 Hypertherm Inc Part Number 810540...
Page 74: ...Appendix E Declaration of Conformity 72 Hypertherm Inc Part Number 810540...
Page 75: ...Appendix E Declaration of Conformity 73 Hypertherm Inc Part Number 810540...